12.8 The 60 mile, 115 kV line GH (Figure P12.8) is operating with the voltages at each end 30° out of phase when a three-phase fault occurs at 80% of the distance from bus G. This fault has 12 arc resist- ance. The currents flowing to the fault are as shown and are in per unit at 100 MVA, 115 kV. Z, = 0.365 Z83° - 80% Line to H a=1.96 L-31.42 4-2.60 2-47.76° ZA z Load 4- 4.51 L-40.68° All values in per unit on 100 MVA, 115 kV. FIGURE P12.8 (b) FIGURE 6.13 Distance relay characteristics on the R-X diagram: (a) impedance; (b) mho; (e) offset mhos; (d) lens; (e) simple blinders: () reactance. a. Determine the apparent impedance seen by the distance relays at G for this fault. b. Determine if the zone 1 mho unit at G set for 90% of the line GH can operate on this fault. Assume that the angle of the mho characteristic Tigure 6.12b) is 75°. + Fig. 6.13b c. Detemine the apparent impedance seen by the distance relays at H for this fault.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
I need the answer quickly
12.8 The 60 mile, 115 kV line GH (Figure P12.8) is operating with the
voltages at each end 30° out of phase when a three-phase fault occurs
at 80% of the distance from bus G. This fault has 12 arc resist-
ance. The currents flowing to the fault are as shown and are in per
unit at 100 MVA, 115 kV.
G
Z = 0.365 ZB3°
%3D
80%
Line to H
la= 1.96 Z-31.42°
4-2.60 2-47.76°
ZR
%3D
z Load
-4.51 L-40.68°
Zx
All values in per unit on 100 MVA, 115 kV.
FIGURE P12.8
(b)
FIGURE 6.13 Distance relay charactenstics on the R-X diagram: (a) impedance;
(b) mho; (e) offset mhos; (d) lens; (e) simple blinders; () reactance.
a. Determine the apparent impedance seen by the distance relays at
G for this fault.
b. Determine if the zone I mho unit at G set for 90% of the line GH
can operate on this fault. Assume that the angle of the mho
characteristic Tigurc 6.12b) is 75°. +
Fig. 6.13b
c. Determine the apparent impedance seen by the distance relays at
H for this fault.
Transcribed Image Text:12.8 The 60 mile, 115 kV line GH (Figure P12.8) is operating with the voltages at each end 30° out of phase when a three-phase fault occurs at 80% of the distance from bus G. This fault has 12 arc resist- ance. The currents flowing to the fault are as shown and are in per unit at 100 MVA, 115 kV. G Z = 0.365 ZB3° %3D 80% Line to H la= 1.96 Z-31.42° 4-2.60 2-47.76° ZR %3D z Load -4.51 L-40.68° Zx All values in per unit on 100 MVA, 115 kV. FIGURE P12.8 (b) FIGURE 6.13 Distance relay charactenstics on the R-X diagram: (a) impedance; (b) mho; (e) offset mhos; (d) lens; (e) simple blinders; () reactance. a. Determine the apparent impedance seen by the distance relays at G for this fault. b. Determine if the zone I mho unit at G set for 90% of the line GH can operate on this fault. Assume that the angle of the mho characteristic Tigurc 6.12b) is 75°. + Fig. 6.13b c. Determine the apparent impedance seen by the distance relays at H for this fault.
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,