(11) In a conventional refrigeration cycle which uses Freon- 12 as the refrigerant, the temperature of the evaporating fluid is -20°C. It leaves the evaporator as saturated vapor at -20°C and enters the compressor. The pressure in the condenser is 1.30 MPa. The liquid leaves the condenser and enters the expansion valve at 40°C. It is proposed to modify this cycle by adding a

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter3: Refrigeration And Refrigerants
Section: Chapter Questions
Problem 12RQ: The condensing pressure is 260 psig and the condenser outlet temperature is 108F for R-22. By how...
icon
Related questions
Question

11. Use ASHRAE Table and Ph diagram 2019

heat exchanger that would superheat the suction vapor to 25°C.
Compare the coefficient of performance of these two cycles. What
is the temperature of the refrigerant entering the expansion valve
with the heat exchanger? For a load of 50kW, determine the
volume flow rate for both cycles.
Ans. 2.79, 2.80, 12°C, 0.0522m³/s, 0.0523 m³/s
Transcribed Image Text:heat exchanger that would superheat the suction vapor to 25°C. Compare the coefficient of performance of these two cycles. What is the temperature of the refrigerant entering the expansion valve with the heat exchanger? For a load of 50kW, determine the volume flow rate for both cycles. Ans. 2.79, 2.80, 12°C, 0.0522m³/s, 0.0523 m³/s
(11) In a conventional refrigeration cycle which uses Freon-
12 as the refrigerant, the temperature of the evaporating fluid
is -20°C. It leaves the evaporator as saturated vapor at -20°C
and enters the compressor. The pressure in the condenser is 1.30
MPa. The liquid leaves the condenser and enters the expansion
valve at 40°C. It is proposed to modify this cycle by adding a
Transcribed Image Text:(11) In a conventional refrigeration cycle which uses Freon- 12 as the refrigerant, the temperature of the evaporating fluid is -20°C. It leaves the evaporator as saturated vapor at -20°C and enters the compressor. The pressure in the condenser is 1.30 MPa. The liquid leaves the condenser and enters the expansion valve at 40°C. It is proposed to modify this cycle by adding a
Expert Solution
steps

Step by step

Solved in 4 steps with 1 images

Blurred answer
Knowledge Booster
Refrigeration and Air Conditioning
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning