Concept explainers
Is it permissible to install a recessed luminaire directly against wood ceiling joists when the label on the luminaire does not indicate that the luminaire is suitable for insulation to be in direct contact with the luminaire? This is a Type Non-IC fixture.
Find whether the recessed luminaire is permitted to directly install against a wood ceiling joist when the label on the luminaire does not indicate that it can be used for insulation in contact with the recessed luminaire.
Answer to Problem 1R
No, the recessed luminaire is not permitted to directly install against a wood ceiling joist when the label on the luminaire does not indicate that it can be used for insulation in contact with the recessed luminaire.
Explanation of Solution
Discussion:
The National Electrical Code committee develops NEC – the standard electrical code and the main objective for the origin of the code is to protect and safeguard the person and elements from electrical hazards. The codes for clearance and installation of luminaire are defined in an article NEC 410.116.
According to an article NEC 410.116(A)(1), for Non-Type Insulated Contact(IC), the recessed luminaire which is not identified for the contact with the insulation should have recessed parts that are spaced not less than
The trim finishing and points of support of the openings in the walls, ceilings, or the other finished surfaces are allowed to be in contact with the combustible materials. Therefore, the recessed luminaire is not permitted to directly install against the wood ceiling joists when the label is not indicated on the luminaire.
Conclusion:
Thus, the recessed luminaire is not permitted to directly install against a wood ceiling joist when the label on the luminaire does not indicate that it can be used for insulation in direct contact with the recessed luminaire.
Want to see more full solutions like this?
Chapter 7 Solutions
Electrical Wiring Residential
Additional Engineering Textbook Solutions
Vector Mechanics for Engineers: Statics and Dynamics
Mechanics of Materials (10th Edition)
Database Concepts (8th Edition)
Electric Circuits. (11th Edition)
SURVEY OF OPERATING SYSTEMS
Concepts Of Programming Languages
- How many spaces does a 3-pole circuit breaker take up in an electrical panel?arrow_forwardIf the cable in Figure ran for the whole of its length, grouped with others of the same size in a high ambient temperature, and was totally surrounded with thermal insulation, The correction factors considered will be----------- Fuseboard High ambient temperature Cable Grouping of cables Thermal insulation Load BS 3036 fuse O a. Cg O b. All Ca,Cg.Ci and Cf O c. Ci O d. Caarrow_forwardCircle the correct answer for the following statements. a. When selecting a trim for a recessed incandescent luminaire, select any trim that physically fits and can be attached to the luminaire. (True) (False) b. When selecting a trim for a recessed incandescent luminaire, select a trim that the manufacturer indicates may be used with that luminaire. (True) (False)arrow_forward
- A 4 in. 1 in. octagon box has one cable clamp and one luminaire stud. How many 14 AWG conductors are permitted? ____________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________arrow_forwardExplain the method of carrying out insulation resistance test on an electrical installationarrow_forwardladder diagram for three circuits, circuit A is one lampholder and one duplex receptacle controlled by a single pole switch, circuit B is a single pole switch controlling the top half of a duplex receptacle that when energized, is indicated by a pilot light at the single pole switch location plus an isolated ground duplex receptacle that is always hot, circuit C is the bottom half of the switched receptacle on circuit B is to be always hot plus another duplex receptacle that is controlled from two locations using coast 3-way wiring system two circuits are 3-wire multiwire branch circuitarrow_forward
- i need the answer quicklyarrow_forwardGrounding lighting fixtures. Threre are specific requirements for grounding lighting fixtures. How must they be grounded and with what size conductors?arrow_forwardGrounding Lighting Fixtures. There are specific requirements for grounding lighting fixtures. How must they be grounded and with what size conductors? Be sure and cite the code in your answers.arrow_forward
- 7.a. Which of the following tests must be performed on a de-energized circuit? A. Power test B. Continuity test C. Voltage test D. Current test 7. Each outside receptacle must be protected by A. a GFCI. B. its own ground rod. C. a single- or double-pole switch. D. its own circuit.arrow_forwardQUESTION 12 What is the minimum sized IMC conduit we should use for the above wire run if it is 24 inches long? a 1/2" b 3/4" c 1" d 1 1/4"arrow_forwardexplain the LIGHTING FIXTURES INSTALLATIONarrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENTElectricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage Learning