Textbook Question
Chapter 28, Problem 16R
While working on the main panelboard that is energized, the electrician inadvertently causes a direct short circuit (line to ground) on one of the branch-circuit breakers. The available fault current at the main service equipment is rather high. The panelboard is labelled “Series-Connected.” The main breaker is rated 100 amperes. Both branch-circuit breaker and main breaker trip OFF. This condition is referred to as being (selective) (nonselective). (Circle the correct answer.)
Expert Solution & Answer
Trending nowThis is a popular solution!
Students have asked these similar questions
Which term is synonymous with short-circuit current rating? A. Fuse rating b. Fault rating c. Withstand rating d. Breaker rating
h.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0.
h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.
Explain the concept of a circuit breaker in electrical power systems and its role in protecting against overcurrent faults.
Chapter 28 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Ch. 28 - What is the minimum size service for a one-family...Ch. 28 - Prob. 2RCh. 28 - Prob. 3RCh. 28 - Prob. 4RCh. 28 - Prob. 5RCh. 28 - Prob. 6RCh. 28 - Prob. 7RCh. 28 - List the standard sizes of fuses and circuit...Ch. 28 - Prob. 9RCh. 28 - Using the method shown in this unit, what is the...
Ch. 28 - State four possible combinations of service...Ch. 28 - Which Code section states that all overcurrent...Ch. 28 - All electrical components have some sort of...Ch. 28 - Arc-fault damage is closely related to the value...Ch. 28 - The utility company has provided a letter to the...Ch. 28 - While working on the main panelboard that is...Ch. 28 - Repeat problem 16 for a main service panel that...Ch. 28 - NEC ______________________________ generally...Ch. 28 - Prob. 19RCh. 28 - Prob. 20RCh. 28 - Overcurrent devices must be accessible. (True)...
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Similar questions
- a) Classify the four categories of 3 phase power system faults we experience in our electrical power industry. b) Explain the emergence of such power systems fault as required in (question 1a)? c) Point out each type of fault specified under (a). d) Produce the (1D) design of the three-phase star connected faults stated under(b)arrow_forwardWhat are three variables that must be considered before installing a circuit breaker?arrow_forwardWhat is a ground fault?arrow_forward
- Explain the purpose and operation of circuit breakers in power systems and their importance in fault protection.arrow_forwardThe load current in a system is 100 A. the short-circuit current for the smallest fault is 100 A. An overcurrent capable of carrying a current of 5 A continuously is to be used. (a) Suggest a suitable C.T. ratio (b) What will be the current for the smallest fault? (c) Will the protective C.T be able to faithfully reproduce the fault current?arrow_forwardDescribe how a fault in long cable can be detected and located using partial discharge technique High voltage engineeringarrow_forward
- X.a- The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.arrow_forward7- What is the uses of circuit breaker?arrow_forward25) What is the type of electrical fault shown in the diagram : XA) Phase to phase to ground. (B) Phase to ground. (C) Three phase short circuit. (D) Single Phase to phase.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENTElectricity for Refrigeration, Heating, and Air C...Mechanical EngineeringISBN:9781337399128Author:Russell E. SmithPublisher:Cengage LearningPower System Analysis and Design (MindTap Course ...Electrical EngineeringISBN:9781305632134Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. SarmaPublisher:Cengage Learning
- Delmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage Learning
EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Electricity for Refrigeration, Heating, and Air C...
Mechanical Engineering
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Cengage Learning
Power System Analysis and Design (MindTap Course ...
Electrical Engineering
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:Cengage Learning
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Cengage Learning
Fault Analysis in Power Systems part 1a; Author: GeneralPAC: Power System Tutorials;https://www.youtube.com/watch?v=g8itg4MOjok;License: Standard youtube license