a.
Whether is it necessary to add air-conditioner load and electric heating load to obtain the combined load on the system.
a.

Answer to Problem 1R
No, it is not necessary to add air-conditioner load and electric heating load to obtain the combined load on the system.
Explanation of Solution
Description:
From NEC 220.60, it is not necessary to add air-conditioner load and electric heating load to obtain the combined load on the system.
Conclusion:
No, it is not necessary to add air-conditioner load and electric heating load to obtain the combined load on the system.
b.
Explain the reason why it is not necessary to add air-conditioner load and electric heating load to obtain the combined load on the system.
b.

Explanation of Solution
Description:
The National Electrical Code (NEC) is the basic standard code and it sets the standards for
From NEC 220.60, the noncoincident loads such as electric heating and air-conditioner are not operated at the same time. Therefore, when calculating the feeder value that is used to supply both the loads, the larger value of loads can be considered.
Therefore, it is not necessary to add air-conditioner load and electric heating load to obtain the combined load on the system.
Conclusion:
Thus, the reason why it is not necessary to add air-conditioner load and electric heating load to obtain the combined load on the system is explained.
Want to see more full solutions like this?
Chapter 23 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
- Use Newton-Raphson method to solve the system x² - 2x-y+0.5= 0 x² + 4y² 4 = 0 - with the starting value (xo,yo) = (2,0.25) and two iteration number.arrow_forwardReversing 3⍉ Motors using manual starters with wiring diagram of forward contacts and reverse contacts.arrow_forwardDetermine (a) the input impedance and (b) the reflectedimpedance, both at terminals (a,b) in the circuit of Fig. P11.14.arrow_forward
- 11.4 Determine Vout in the circuit shown in Fig. P11.4.arrow_forwardFor the circuit in Fig. P11.1, determine (a) iL(t) and (b) theaverage power dissipated in RL.arrow_forwardDesign a synchronous Up/Down counter to produce the following sequence (4 9 2,0,7,6,3,1,5) using T flip-flop. The counter should count up when Up/Down =1, and down when Up/Down = 0.arrow_forward
- Solve the following systems using Gauss Seidal and Jacobi iteration methods for n=8 and initial values X0=(000). - 2x16x2 x3 = -38 - -3x1 x2+7x3 = −34 -8x1 + x2 - 2x3 = -20arrow_forwardSolve the following systems using Gauss Seidal and Jacobi iteration methods for n=8 and initial values Xº=(000). 3x12x2x3 = 4 - 2x1 x2 + 2x3 = 10 x13x24x3 = 4arrow_forwardUse Newton-Raphson method to solve the system x² - 2x-y+0.5= 0 x² + 4y² 4 = 0 - with the starting value (xo,yo) = (2,0.25) and two iteration number.arrow_forward
- Solve the following systems using Gauss Seidal and Jacobi iteration methods for n=8 and initial values X0=(000). - 2x16x2 x3 = -38 - -3x1 x2+7x3 = −34 -8x1 + x2 - 2x3 = -20arrow_forwardSolve the following nonlinear system using Newton's method 1 f1(x1, x2, x3)=3x₁ = cos(x2x3) - - 2 f2(x1, x2, x3) = x² - 81(x2 +0.1)² + sin x3 + 1.06 f3(x1, x2, x3) = ex1x2 +20x3 + Using x (0) X1 X2 X3 10π-3 3 = 0.1, 0.1, 0.1 as initial conditioarrow_forwardA single phase a.c. distributor AB has: The distance from A to B is 500 m. The distance from A to C is 800 m. The impedance of each section is (6+j 8) /km. A B C The voltage at the far end is maintained at 250 volt. Find: sending voltage, sending current, supply power factor and 80 A 60 A total voltage drop. 0.8 lag. P.f 0.6 lead. p.farrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT