Question
Book Icon
Chapter 23, Problem 23.18P
To determine

The correct readings of rod which are necessary on the batter board tops to set them properly.

  5.61ft

Given:

Floor elevation 1069.31ft

Benchmark A=1070.58ft

Sight A=5.34ft

Concept Used:

This is one more method of layout of buildings, is to stake two points on the building, one of them with the total station instrument, take a backsight on the other and stack all the remaining points from that setup using pre -calculated angles and distances.

Calculation:

Calculate the height of instrument by adding bench mark A and sight A :

  HI=1070.58+5.34HI=1075.92ft

Calculate the elevation value for batter roads by using the formula:

  Eb=Floor elevation+1 ftEb=1069.31+1Eb=1070.31ft

Now, we must determine the rod reading value at the batter rods by:

  Sbb=EbHISbb=1070.311075.92Sbb=5.61ft

Conclusion:

Therefore, the rod readings are necessary on the batter board tops to set them properly is 5.61ft .

Blurred answer
Students have asked these similar questions
Figure shows a tunnel section on the Colorado River Aqueduct. The area of the water cross section is 191 ft 2 , and the wetted perimeter is 39.1 ft. The flow is 1600 cfs. If n=0.013 for the concrete lining, find the slope.
7.48 An engineer is making an estimate for a home owner. This owner has a small stream (Q= 1.4 cfs, T = 40°F) that is located at an elevation H = 34 ft above the owner's residence. The owner is proposing to dam the stream, diverting the flow through a pipe (penstock). This flow will spin a hydraulic turbine, which in turn will drive a generator to produce electrical power. Estimate the maximum power in kilowatts that can be generated if there is no head loss and both the turbine and generator are 100% efficient. Also, estimate the power if the head loss is 5.5 ft, the turbine is 70% efficient, and the generator is 90% efficient. Penstock Turbine and generator Problem 7.48
design rectangular sections for the beam and loads, and p values shown. Beam weights are not included in the loads given. Show sketches of cross sections including bar sizes, arrangements, and spacing. Assume concrete weighs 23.5 kN/m'. fy= 420 MPa, and f’c= 21 MPa.Show the shear and moment diagrams as well
Knowledge Booster
Background pattern image
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Structural Analysis
Civil Engineering
ISBN:9781337630931
Author:KASSIMALI, Aslam.
Publisher:Cengage,
Text book image
Structural Analysis (10th Edition)
Civil Engineering
ISBN:9780134610672
Author:Russell C. Hibbeler
Publisher:PEARSON
Text book image
Principles of Foundation Engineering (MindTap Cou...
Civil Engineering
ISBN:9781337705028
Author:Braja M. Das, Nagaratnam Sivakugan
Publisher:Cengage Learning
Text book image
Fundamentals of Structural Analysis
Civil Engineering
ISBN:9780073398006
Author:Kenneth M. Leet Emeritus, Chia-Ming Uang, Joel Lanning
Publisher:McGraw-Hill Education
Text book image
Sustainable Energy
Civil Engineering
ISBN:9781337551663
Author:DUNLAP, Richard A.
Publisher:Cengage,
Text book image
Traffic and Highway Engineering
Civil Engineering
ISBN:9781305156241
Author:Garber, Nicholas J.
Publisher:Cengage Learning