Concept explainers
(a)
Calculate the design wind load, base shear, and overturning moment.
(a)

Answer to Problem 18P
The resultant force acting on roof slab is
The resultant force acting on second floor is
The seismic base shear is
The overturning moment is
Explanation of Solution
Given information:
The importance factor (I) is 1.15.
The value of
The mean roof height is 30 ft.
The height of the single floor (h) is 15 ft.
The basic wind speed is
The exposure is D.
Calculation:
Consider the exposure of the D.
Refer Table 2.9, “Adjustment factor
The value of
Calculate the design wind pressure as shown below.
Refer Table 2.8 “Simplified horizontal design wind pressure
Calculate the design wind pressures for zone A and zone C as shown in Table 1.
Zone | ||
A | 12.8 | 24.44 |
C | 8.5 | 16.23 |
Calculate the resultant force for each level as shown below.
The distance at which the load acts for zone A is
The distance at which the load acts for zone C is
Calculate the resultant force acting on roof slab as shown below.
Hence, the resultant force acting on roof slab
Calculate the resultant force acting on second floor as shown below.
Hence, the resultant force acting on second floor
Calculate the base shear force as shown below.
Hence, the seismic base shear is
Calculate the overturning moment as shown below.
Therefore, the overturning moment is
(b)
Calculate the base shear and overturning moment using the equivalent lateral force procedure.
(b)

Answer to Problem 18P
The seismic base shear is
The overturning moment is
Explanation of Solution
Given information:
The average weight of the floor and roof is
The value of
The value of
The value of R is 8.
The importance factor (I) is 1.5.
Calculation:
The value of
Calculate the fundamental period as shown below.
Calculate the total dead load of the building as shown below.
Calculate the magnitude of the base shear as shown below.
Calculate the magnitude of the maximum base shear as shown below.
Calculate the magnitude of the minimum base shear as shown below.
Hence, take the value of
The value of k is 1 for
Calculate the seismic base shear to each floor level as shown below.
Provide the calculated the seismic base shear at each floor levels as shown in Table 1.
Floor | Weight | Height of the floor | |||
Roof | 900 | 30 | 27, 000 | 0.667 | 39.5 |
2nd | 900 | 15 | 13,500 | 0.333 | 19.7 |
Sum | 1,800 | 40,500 | 59.2 |
Refer to Table 1:
The seismic base shear is
Hence, the seismic base shear is
Calculate the overturning moment as shown below.
Therefore, the overturning moment is
(c)
Provide the design strength of the building govern the wind force of seismic force.
(c)

Answer to Problem 18P
The design strength of the building governed by the seismic force.
Explanation of Solution
Given information:
The average weight of the floor and roof is
The value of
The value of
The value of R is 8.
The importance factor (I) is 1.5.
Calculation:
Refer to part (a).
The seismic base shear and overturning moment due to wind force.
The seismic base shear is
The overturning moment is
Refer to part (b).
The seismic base shear and overturning moment due to seismic force.
The seismic base shear is
The overturning moment is
The seismic base shear and overturning moment due to seismic force is greater than to compared with the seismic base shear and overturning moment due to seismic force.
Hence, the design strength of the building governed by the seismic force.
Want to see more full solutions like this?
Chapter 2 Solutions
UCD FUND OF STRUCTURAL ANALYSIS 5E
- 7.69 Assume that the head loss in the pipe is given by h₁ = 0.014(L/D) (V²/2g), where L is the length of pipe and D is the pipe diameter. Assume α = 1.0 at all locations. a. Determine the discharge of water through this system. b. Draw the HGL and the EGL for the system. c. Locate the point of maximum pressure. d. Locate the point of minimum pressure. e. Calculate the maximum and minimum pressures in the system. Elevation 100 m Water T = 10°C L = 100 m D = 60 cm Elevation 95 m Elevation 100 m L = 400 m D = 60 cm Elevation = 30 m Nozzle 30 cm diameter jet Problem 7.69arrow_forwardA rectangular flume of planed timber (n=0.012) slopes 0.5 ft per 1000 ft. (i)Compute the discharge if the width is 7 ft and the depth of water is 3.5 ft. (ii) What would be thedischarge if the width were 3.5 ft and depth of water is 7 ft? (iii) Which of the two forms wouldhave greater capacity and which would require less lumber?arrow_forwardFigure shows a tunnel section on the Colorado River Aqueduct. The area of the water cross section is 191 ft 2 , and the wetted perimeter is 39.1 ft. The flow is 1600 cfs. If n=0.013 for the concrete lining, find the slope.arrow_forward
- 7.48 An engineer is making an estimate for a home owner. This owner has a small stream (Q= 1.4 cfs, T = 40°F) that is located at an elevation H = 34 ft above the owner's residence. The owner is proposing to dam the stream, diverting the flow through a pipe (penstock). This flow will spin a hydraulic turbine, which in turn will drive a generator to produce electrical power. Estimate the maximum power in kilowatts that can be generated if there is no head loss and both the turbine and generator are 100% efficient. Also, estimate the power if the head loss is 5.5 ft, the turbine is 70% efficient, and the generator is 90% efficient. Penstock Turbine and generator Problem 7.48arrow_forwarddesign rectangular sections for the beam and loads, and p values shown. Beam weights are not included in the loads given. Show sketches of cross sections including bar sizes, arrangements, and spacing. Assume concrete weighs 23.5 kN/m'. fy= 420 MPa, and f’c= 21 MPa.Show the shear and moment diagrams as wellarrow_forwardDraw as a 3D object/Isometricarrow_forward
- Post-tensioned AASHTO Type II girders are to be used to support a deck with unsupported span equal to 10 meters. Two levels of Grade 250, 10 x 15.2 mm Ø 7-wire strand are used to tension the girders with 5 tendons per level, where the tendons on top stressed before the ones on the bottom. The girder is simply supported at both ends. The anchors are located 100 mm above the neutral axis at the supports while the eccentricity is measured at 400 mm at the midspan. The tendon profile follows a parabolic shape using a rigid metal sheathing. A concrete topping (slab) 130 mm thick is placed above the beam with a total tributary width of 4 meters. Use maximum values for ranges (table values). Assume that the critical section of the beam is at 0.45LDetermine the losses (friction loss, anchorage, elastic shortening, creep, shrinkage, relaxation). Determine the stresses at the top fibers @ critical section before placing a concrete topping, right after stress transfer. Determine the stress at the…arrow_forwardPlease solve this question in hand writting step by step with diagram drawingarrow_forwardSolve this question pleasearrow_forward
- Please draw shear and moment diagrams with provided information.arrow_forwardShow step by step solutionarrow_forwardDraw the shear and the moment diagrams for each of the frames below. If the frame is statically indeterminate the reactions have been provided. Problem 1 (Assume pin connections at A, B and C). 30 kN 2 m 5 m 30 kN/m B 60 kN 2 m 2 m A 22 CO Carrow_forward
- Structural Analysis (10th Edition)Civil EngineeringISBN:9780134610672Author:Russell C. HibbelerPublisher:PEARSONPrinciples of Foundation Engineering (MindTap Cou...Civil EngineeringISBN:9781337705028Author:Braja M. Das, Nagaratnam SivakuganPublisher:Cengage Learning
- Fundamentals of Structural AnalysisCivil EngineeringISBN:9780073398006Author:Kenneth M. Leet Emeritus, Chia-Ming Uang, Joel LanningPublisher:McGraw-Hill EducationTraffic and Highway EngineeringCivil EngineeringISBN:9781305156241Author:Garber, Nicholas J.Publisher:Cengage Learning





