Inductive Circuits
Fill in all the missing values. Refer to the following formulas:
Inductance (H) | Frequency (Hz) | Inductive Reactance (
|
1.2 | 60 | |
0.085 | 213.628 | |
1000 | 4712.389 | |
0.65 | 600 | |
3.6 | 678.584 | |
25 | 411.459 | |
0.5 | 60 | |
0.85 | 6408.849 | |
20 | 201.062 | |
0.45 | 400 | |
4.8 | 2412.743 | |
1000 | 40.841 |

The missing values in the table.
Answer to Problem 1PP
Inductance (H) | Frequency(Hz) | Inductive Reactance(Ω) |
1.2 | 60 | 452.39 |
0.085 | 400 | 213.628 |
0.75 | 1000 | 4712.389 |
0.65 | 600 | 2450.44 |
3.6 | 30 | 678.584 |
2.61 | 25 | 411.459 |
0.5 | 60 | 188.50 |
0.85 | 1200 | 6408.849 |
1.6 | 20 | 201.062 |
0.45 | 400 | 1130 |
4.8 | 80 | 2412.743 |
6.44m | 1000 | 40.841 |
Explanation of Solution
We are given the following formulae,
Want to see more full solutions like this?
Chapter 17 Solutions
Delmar's Standard Textbook of Electricity (MindTap Course List)
- Please solutionarrow_forwardUse data sheet B on page 383 to draw the wiring diagram. Note: use only the number of contacts required. First 1. Wire the motor to operate in forward and reverse at 115 VAC.arrow_forwardB:A 20 MVA transformer which may be called upon to operate at 30% overload, feeds 11 KV busbars through a circuit breaker: other circuit breakers supply outgoing feeders. The transformer circuit breaker is equipped with 1000/5 A CTS and the feeder circuit breakers with 400/5 A CTS and all sets of CTs feed induction type over current relays. The relays on the feeder circuits breakers have a 125% plug setting, and 0.3 time setting. If 3 ph fault current of 5000 A flows from the transformer to one of the feeders, find the operating time of the feeder relay, the minimum plug setting of the transformer relay and its time setting assuming a discrimination time margin of 0.5 sec. Relays having the following characteristics for TMS=1 PSM T in sec. 2 3.6 5 10 15 20 10 6 3.9 2.8 2.2 2.1arrow_forward
- 10.34 Determine the power readings of the two wattmetersshown in the circuit of Fig. P10.34 given that ZY = (15− j5) Warrow_forward10.29 A 208-V (rms) balanced three-phase source supports twoloads connected in parallel. Each load is itself a balanced threephaseload. Determine the line current, given that load 1 is 12 kVAat pf 1 = 0.7 leading and load 2 is 18 kVA at pf 2 = 0.9 lagging.arrow_forward10.31 A 240-V (rms), 60-Hz Y-source is connected to a balancedthree-phase Y-load by four wires, one of which is the neutral wire.If the load is 400 kVA at pf old = 0.6 lagging, what size capacitorsshould be added to change the power factor to pf new = 0.95lagging?arrow_forward
- Delmar's Standard Textbook Of ElectricityElectrical EngineeringISBN:9781337900348Author:Stephen L. HermanPublisher:Cengage Learning