Based on the total estimated load calculations, what is the current draw on the Study/Bedroom circuit? __________________________________________________________
Calculate the current drawn on the Study/Bedroom circuit based on the total estimated load calculations.
Answer to Problem 1R
The current draw on the Study/Bedroom circuit based on the total estimated load calculations is 9.4 amperes.
Explanation of Solution
Formula used:
Write the general expression to calculate the VOLT-AMPERES for single-phase.
Here,
E is the supply voltage, and
I is the current.
Rearrange the equation (1) to find the current I in amperes.
Calculation:
Refer to Table 14-1 in the textbook.
The total estimated load in VA for the Study/Bedroom outlet count in Circuit A21 is 1125 VA.
The single-phase supply voltage (E) is 120 V.
Substitute 1125 VA for VOLT-AMPERES and 120 V for E in equation (2) to find the current I in amperes.
Conclusion:
Thus, the current draw on the Study/Bedroom circuit based on the total estimated load calculations is 9.4 amperes.
Want to see more full solutions like this?
Chapter 14 Solutions
EBK ELECTRICAL WIRING RESIDENTIAL
Additional Engineering Textbook Solutions
Concepts Of Programming Languages
Automotive Technology: Principles, Diagnosis, And Service (6th Edition) (halderman Automotive Series)
Web Development and Design Foundations with HTML5 (8th Edition)
Starting Out With Visual Basic (8th Edition)
SURVEY OF OPERATING SYSTEMS
Starting Out with Java: From Control Structures through Objects (7th Edition) (What's New in Computer Science)
- ___________ is an Area on a device characteristic where the ratio between applied voltage and resulting current is constant.arrow_forwardf.1. Since the footing or foundation is generally part of the grounding electrode system, the _______electrode is one of the first electrodes installed.A. metal water pipeB. plateC. concrete-encasedD. ground ringf.2. When you're connecting the grounding electrode conductor to a metal water pipe as it enters a building,the connection must be made within _______ feet of the pipe's entrance to the building.A. 10B. 5C. 15D. 7f.3. Which National Electrical Code table is used for sizing grounding electrode conductors?A. Table 250.102(C)(1)B. Table 250.66C. Table 250.122D. Table 250.118(6)(a)arrow_forwardWhat follows is a numeric fill in the blank question with 3 blanks. Figure 1 shows the three phases V-t graph in Turkey. Please write the indicated values with their units in boxes and Voltage - time function of each phase in table below. Please write the units in the second box. 1= _______________ V 2= ________________ms 3= _______________msarrow_forward
- Fill in the blanks. One of electrical wiring design procedure is that circuit all ____________ and __________ to the appropriate panels and prepare the panel schedule.arrow_forwardWhen used as service equipment, a panelboard (load center) must be ______________________ that is suitable for use as service equipment, 230.66. If the panelboard (load center) contains the main service disconnect, it must be clearly marked ____________________________________, 230.70(B).arrow_forward1.1 PV modules can be wired together in an array using ______ connections to increase voltage. a. Terminating b. Series c. Parallel d. AC 1.2 A PV module, also called a solar panel, is comprised of individual photovoltaic _______ wired and mounted together as an integrated unit. a. Capsules b. Compartments c. Chips d. Cells 1.3 A __________ system uses a storage system that stores the generated electricity so it can provide during times when the system’s panels are not receiving solar energy. a. Direct coupled b. Self regulating c. Charge controlled d. Indirectly connected 1. 4 __________ energy may have the potential to supply all of the world's energy needs, but at this time, it provides a very small percentage. a. Coal b. Natural Gas c. Diesel d. Solararrow_forward
- If two 115-volt loads were connectedin parallel with 240 volts, they would__________.a. burn dimlyb. immediately burn outc. burn correctlyd. none of the abovearrow_forwardGood practice suggests that the load should not exceed 1600 Watts for a 20 Amperes circuit (max of 80 sq.m.) and____ Watts for a 15 Amperes circuit (maxof 60 sq.m.).arrow_forwardAn open in one of the heated rear window grid elements can be repaired by ______. a. pealing the heat grid off the glass with a heat gun and installing a new grid element b. applying a thin strip of a repair compound to the damaged area c. bridging the damaged area with rosin core solder d. replacing the window glassarrow_forward
- of p o How many conductors enter the ceiling fan/light wall box? Switch ond out let boxes s tirst 10. What type and size of box may be used for the ceiling fan/light wall box?. 11. What type of covers are used with 4 in. square outlet boxes? 12. a. Does the circuit for the Master Bedroom have a grounded circuit conductor? b. Does it have an equipment grounding conductor? c. Explain the difference between a "grounded" conductor and an "equipment grounding" conductor. 13. Approximately how many feet (meters) of 2-wire cable and 3-wire cable are needed to ft complete the circuit supplying the Master Bedroom? Two-wire cable: ft (- m). m). Three-wire cable: 14. If the cable is laid in notches in the corner studs, what protection for the cable must be provided? 15. How high are the receptacles mounted above the finished floor in this bedroom? 16. Approximately how far from the bedroom door is the first receptacle mounted? (See the plans.) 17. What is the distance from the finished floor to…arrow_forwardEquipment Grounding 13. A metal elbow is a part of a nonmetallic, underground raceway. The elbow won't need to be grounded as long as it's encased in at least _______ inches of concrete. A. 4 B. 5 C. 2 D. 6 13 A. Which of the following can be in the form of a wire and is required to be installed with feeders and branch circuits? A. Phased neutral conductorB. Equipment grounding conductor C. Grounded neutral conductorD. Grounding electrode conductorarrow_forwardIf the total computed load of a residence is 45,840 volt-amperes, the computed amperage of the residence is __________ ampsarrow_forward
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT