Discuss the importance of power-factor correction in a.c. systems. A 400 V, 50 Hz, three-phase distribution system supplies a 20 kVA, three-phase induction motor load at a power factor of 0.8 lagging, and a star-connected set of impedances, each having a resistance of 10 Ω and an inductive reactance of 8 Ω. Calculate the capacitance of delta-connected capacitors required to improve the overall power factor to 0.95 lagging. ANS: 75 µF/ph
A 3-phase, wye-connected generator induces 2400 V in each of its windings. Calculate the line voltage.