
Business Driven Information Systems
5th Edition
ISBN: 9780073402987
Author: Paige Baltzan Instructor, Amy Phillips Professor
Publisher: McGraw-Hill Education
expand_more
expand_more
format_list_bulleted
Question
Chapter 1, Problem 1EC
To determine
The business I will build throughout the course and to identify a name for the business.
Expert Solution & Answer

Want to see the full answer?
Check out a sample textbook solution
Students have asked these similar questions
Q1.
Consider a single-phase step-down transformer with primary and
secondary turns of 600 and 100 respectively and a primary voltage of
11 kV.
(i) An open circuit test was conducted on the transformer and the primary
current was measured as:
I₁ = 2.20 A
Use these results to calculate the magnetising reactance in the equivalent
circuit (X) given that Rm, representing the core loss, has a value of 21 km.
(ii) The remaining equivalent circuit parameters are as follows:
R₁ = 40, X₁ = 25 N, R₂ = 0.4 N, X₂ = 0.3 N
Draw the complete simplified equivalent circuit, by referring series
components on the primary side to the secondary, giving all component
values.
(iii) The transformer is connected, on its secondary side, to a load of 10
at a power factor of 1. Calculate the voltage across the load.
(iv) Calculate the efficiency of the transformer when operating at the load
given in part (iii).
b)
A 132 kV supply feeds a line of reactance 15 which is connected to a 100
MVA, 132/33 kV transformer of 0.08 p.u. reactance as shown in the
Figure 2. The transformer feeds a 33 kV line of reactance 8 Q, which, in
turn, is connected to a 75 MVA, 33/11 KV transformer of 0.12 p.u.
reactance. The transformer supplies an 11 KV substation from which a local
11 kV feeder of 4 Q reactance is supplied.
T1
T2
132 kV
33 kV
11 kV
Fault
X
CB
Relay
Figure 2. Network for Q4 b).
(i) Given the system base of 100 MVA, compute the total equivalent
reactance of the radial circuit in per unit (p.u.).
(ii) Determine the three-phase fault current at the load end of the 11 kV
feeder, assuming a fault impedance of 0.05 Q. Calculate the fault
current in Amperes.
(iii) The 11 kV feeder connects to a protective overcurrent relay via 200/5 A
current transformers. This relay has a standard normally inverse IDMT
characteristic, with a setting current of 3 A and a time multiplier setting
of 0.4. Calculate the…
Q2.
a) Two three-phase transformers, designated A and B, have the following
secondary equivalent circuit parameters per phase:
R₁ = 0.002 Q, XA = 0.03 Q, RB = 0.004 Q, X = 0.012 Q
Transformer A is 250 kVA and transformer B is 450 kVA. Calculate how
they share a load of 650 KVA when connected in parallel (assume the
voltage ratios are equal)
b) A step-up transformer is being specified for the beginning of a 3-phase, 4
wire high voltage transmission line. Discuss your recommendation for the
configuration of the transformer connections on both the primary and
secondary side of the transformer.
c)
Define power system protection and describe its fundamental purpose.
Discuss the following key concepts including discrimination, stability,
speed of operation, sensitivity, and reliability in the context of the power
system protection components and schemes.
Chapter 1 Solutions
Business Driven Information Systems
Ch. 1 - Prob. 1OCQCh. 1 - Prob. 2OCQCh. 1 - Prob. 3OCQCh. 1 - Prob. 4OCQCh. 1 - Prob. 5OCQCh. 1 - Prob. 6OCQCh. 1 - Prob. 1RQCh. 1 - Prob. 2RQCh. 1 - Prob. 3RQCh. 1 - Prob. 4RQ
Ch. 1 - Prob. 5RQCh. 1 - Prob. 6RQCh. 1 - Prob. 7RQCh. 1 - Prob. 8RQCh. 1 - Prob. 9RQCh. 1 - Prob. 10RQCh. 1 - Prob. 11RQCh. 1 - Prob. 12RQCh. 1 - Prob. 13RQCh. 1 - Prob. 14RQCh. 1 - Prob. 15RQCh. 1 - Prob. 1CCOCh. 1 - Prob. 2CCOCh. 1 - Prob. 3CCOCh. 1 - Prob. 4CCOCh. 1 - Prob. 5CCOCh. 1 - Prob. 6CCOCh. 1 - Prob. 1CCTCh. 1 - Prob. 2CCTCh. 1 - Prob. 3CCTCh. 1 - Prob. 4CCTCh. 1 - Prob. 5CCTCh. 1 - Prob. 1CBTCh. 1 - Prob. 2CBTCh. 1 - Prob. 3CBTCh. 1 - Prob. 4CBTCh. 1 - Prob. 5CBTCh. 1 - Prob. 6CBTCh. 1 - Prob. 7CBTCh. 1 - Prob. 8CBTCh. 1 - Prob. 9CBTCh. 1 - Prob. 10CBTCh. 1 - Prob. 1ECCh. 1 - Prob. 2ECCh. 1 - Prob. 3ECCh. 1 - Prob. 4ECCh. 1 - Prob. PIAYKBPCh. 1 - Prob. PIIAYKBPCh. 1 - Prob. PIIIAYKBPCh. 1 - Prob. PIVAYKBPCh. 1 - Prob. PVAYKBPCh. 1 - Prob. PVIAYKBPCh. 1 - Prob. PVIIAYKBPCh. 1 - Prob. PVIIIAYKBPCh. 1 - Prob. PIXAYKBP
Knowledge Booster
Similar questions
- Four-bar linkage mechanism, AB=40mm, BC=60mm, CD=70mm, AD=80mm, =60°, w1=10rad/s. Determine the direction and magnitude of w3 using relative motion graphical method. A B 2 3 77777 477777arrow_forwardFour-bar linkage mechanism, AB=40mm, BC=60mm, CD=70mm, AD=80mm, =60°, w1=10rad/s. Determine the direction and magnitude of w3 using relative motion graphical method. A B 2 3 77777 477777arrow_forwardQ3. a) Given the unsymmetrical phasors for a three-phase system, they can be represented in terms of their symmetrical components as follows: [Fa] [1 1 Fb = 1 a² [Fc. 11[Fao] a Fai 1 a a2F a2- where F stands for any three-phase quantity. Conversely, the sequence components can be derived from the unsymmetrical phasors as: [11 1] [Fal Faol Fa1 = 1 a a² F 1 a² a a2. Given the unbalanced three-phase voltages: V₁ = 120/10° V, V₂ = 200/110° V, V = 240/200° V Calculate in polar form the sequence components of the voltage.arrow_forward
- Complete the table of values for this circuit:arrow_forward*P2.58. Solve for the node voltages shown in Figure P2.58. - 10 Ω w + 10 Ω 15 Ω w w '+' 5 Ω 20x 1 A Figure P2.58 w V2 502 12Aarrow_forwardAn average operating data for conventional activated sludge treatment plant is as follows: (1) Wastewater flow, Q = 50000m³/darrow_forward
- A- Design grit removal chamber for a W.W.P with hourly flow equal 5000 m'h B-Answer five of the following: 1-....... is the storm runoff that occurs from rainfall? (15 mark) (10 mark) 2- A protective device used to remove large and coarse materials from the wastewater 3-....... utilize a relative porous bacteria growth medium such as rock or formed plastic shapes 4- There are two basic methods of introducing air into the aeration tanks are....... And ......... 5-..... to water bodies such as rivers will be described by Streeter- Phelp's equation 6- .... is the liquid conveyed by a sewer, it may consist of any one or a mixture of liquid wastes.arrow_forwardAn 18.65 kW, 4-pole, 50 Hz, 3-phase induction motor has friction and windage losses of 2.5% of the output. The full-load slip is 4%. Find for full-load (i) the rotor cu loss (ii) the rotor input power (iii) the output torque.arrow_forwardThe evaporator of a vapor compression refrigeration cycle utilizing R-123 as the refrigerant isbeing used to chill water. The evaporator is a shell and tube heat exchanger with the water flowingthrough the tubes. The water enters the heat exchanger at a temperature of 54°F. The approachtemperature difference of the evaporator is 3°R. The evaporating pressure of the refrigeration cycleis 4.8 psia and the condensing pressure is 75 psia. The refrigerant is flowing through the cycle witha flow rate of 18,000 lbm/hr. The R-123 leaves the evaporator as a saturated vapor and leaves thecondenser as a saturated liquid. Determine the following:a. The outlet temperature of the chilled waterb. The volumetric flow rate of the chilled water (gpm)c. The UA product of the evaporator (Btu/h-°F)d. The heat transfer rate between the refrigerant and the water (tons)arrow_forward
- Q1: Consider the finite state machine logic implementation in Fig. shown below: a. b. Construct the state diagram. Repeat the circuit design using j-k flip flop. C'lk A D 10 Clk Q D 32 Cik O 31 Please solve the question on a sheet of paper by hand and explain everything related to the question step by step.arrow_forwardAnot ined sove in peaper S PU +96 An 18.65 kW, 4-pole, 50 Hz, 3-phase induction motor has friction and windage losses of 2.5% of the output. The full-load slip is 4 %. Find for full-load (i) the rotor cu loss (ii) the rotor input power (iii) the output torque. 750 1 T el Marrow_forwardAlternator has star-connected,4-pole, 50 Hz as the following data: Flux per pole-0.12 Wb; No. of slot/pole/phase=4; conductor/slot=4; Each coil spans 150° (electrical degree) pitches Find (i) number of turns per phase (ii) distribution factor (iii) pitch factor (iv) no-load phase voltage (v) no-load line voltage.arrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- MATLAB: An Introduction with ApplicationsEngineeringISBN:9781119256830Author:Amos GilatPublisher:John Wiley & Sons IncEssentials Of Materials Science And EngineeringEngineeringISBN:9781337385497Author:WRIGHT, Wendelin J.Publisher:Cengage,Industrial Motor ControlEngineeringISBN:9781133691808Author:Stephen HermanPublisher:Cengage Learning
- Basics Of Engineering EconomyEngineeringISBN:9780073376356Author:Leland Blank, Anthony TarquinPublisher:MCGRAW-HILL HIGHER EDUCATIONStructural Steel Design (6th Edition)EngineeringISBN:9780134589657Author:Jack C. McCormac, Stephen F. CsernakPublisher:PEARSONFundamentals of Materials Science and Engineering...EngineeringISBN:9781119175483Author:William D. Callister Jr., David G. RethwischPublisher:WILEY

MATLAB: An Introduction with Applications
Engineering
ISBN:9781119256830
Author:Amos Gilat
Publisher:John Wiley & Sons Inc

Essentials Of Materials Science And Engineering
Engineering
ISBN:9781337385497
Author:WRIGHT, Wendelin J.
Publisher:Cengage,

Industrial Motor Control
Engineering
ISBN:9781133691808
Author:Stephen Herman
Publisher:Cengage Learning

Basics Of Engineering Economy
Engineering
ISBN:9780073376356
Author:Leland Blank, Anthony Tarquin
Publisher:MCGRAW-HILL HIGHER EDUCATION

Structural Steel Design (6th Edition)
Engineering
ISBN:9780134589657
Author:Jack C. McCormac, Stephen F. Csernak
Publisher:PEARSON

Fundamentals of Materials Science and Engineering...
Engineering
ISBN:9781119175483
Author:William D. Callister Jr., David G. Rethwisch
Publisher:WILEY