WO single phase 100 kVA transformers, each having different leakage mpedances are connected in parallel. When a load of 150 kVA at 0.8 pf lagging is pplied * Both transformers will operate at identical power factors. Both transformers will operate at power factor more than 0.8 lagging. One of transformers will operate at pf more than 0.8 lagging and other will operate at pf less than 0.8 lagging. O Both transformers will operate at power factor less than 0.8 lagging.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question

Electrical Apparatus and devices

choose the correct answer and show complete solution

Two single phase 100 kVA transformers, each having different leakage
impedances are connected in parallel. When a load of 150 kVA at 0.8 pf lagging is
applied *
Both transformers will operate at identical power factors.
Both transformers will operate at power factor more than 0.8 lagging.
One of transformers will operate at pf more than 0.8 lagging and other will operate at
pf less than 0.8 lagging.
Both transformers will operate at power factor less than 0.8 lagging.
The daily variation of load on a 100 kVA transformer is as follows: 8:00 am to 1:00
pm - 65 kW, 35 kVAr; 1:00 pm to 6:00 pm - 80 kW, 50 kVAr; 6:00 pm to 1:00 am
- 30 kW, 30 kVAr; 1:00 am to 8:00 am - No-load. This transformer has no-load
core loss of 270 W and a full-load ohmic loss of 1,200 W. Determine the all-day
efficiency of the transformer. *
97.26%
98.26%
O 97%
98%
Transcribed Image Text:Two single phase 100 kVA transformers, each having different leakage impedances are connected in parallel. When a load of 150 kVA at 0.8 pf lagging is applied * Both transformers will operate at identical power factors. Both transformers will operate at power factor more than 0.8 lagging. One of transformers will operate at pf more than 0.8 lagging and other will operate at pf less than 0.8 lagging. Both transformers will operate at power factor less than 0.8 lagging. The daily variation of load on a 100 kVA transformer is as follows: 8:00 am to 1:00 pm - 65 kW, 35 kVAr; 1:00 pm to 6:00 pm - 80 kW, 50 kVAr; 6:00 pm to 1:00 am - 30 kW, 30 kVAr; 1:00 am to 8:00 am - No-load. This transformer has no-load core loss of 270 W and a full-load ohmic loss of 1,200 W. Determine the all-day efficiency of the transformer. * 97.26% 98.26% O 97% 98%
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Protection System for Machines
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,