When EMT is installed in wet locations, all supports, bolts, straps, and screws shall be _____. a. of corrosion-resistant materials b. protected against corrosion by corrosion-resistant materials c. of nonmetallic materials only d. a or b
QUESTION 1
-
When EMT is installed in wet locations, all supports, bolts, straps, and screws shall be _____.
a. of corrosion-resistant materialsb. protected against corrosion by corrosion-resistant materialsc. of nonmetallic materials onlyd. a or b
QUESTION 2
-
EMT shall not be used where _____.
a. subject to severe physical damageb. a and cc. used for the support of luminaires except conduit bodies no larger than the largest trade size of the tubingd. protected from corrosion only by enamel
QUESTION 3
-
Galvanized steel and stainless steel EMT, elbows, couplings, and fittings can be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where _____.
a. listed for wet locationsb. protected by corrosion protectionc. a and bd. approved as suitable for the condition
QUESTION 4
-
The use of EMT shall be permitted for both exposed and concealed work in _____.
a. dry, damp, and wet locationsb. concrete, in direct contact with the earth or in areas subject to severe corrosive influences where installed in accordance with 358.10(B)c. all of thesed. any hazardous (classified) location as permitted by other articles in this Code
QUESTION 5
-
EMT shall not be threaded.
True
False
QUESTION 6
-
Metal faceplates for snap switches, including dimmer and similar control switches, shall be ____.
a. bonded to the grounded electrode
b. bonded to the grounded electrode and grounded
c. none of these
d. grounded
QUESTION 7
-
Switches and circuit breakers used as switches shall be installed so that they may be operated from a readily accessible place.
True
False
QUESTION 8
-
A snap switch with an integral nonmetallic enclosure complying with 300.15(E) is required to be connected to an equipment grounding conductor.
True
False
QUESTION 9
-
Switches controlling line-to-neutral lighting loads shall have a grounded conductor provided at the switch location unless the _____.
a. conductors enter the device box through a raceway that has sufficient area to accommodate a grounded conductor or box enclosing the switch is accessible for the installation of an additional or replacement cable without removing finish materials
b. conductors enter the device box through a raceway that has sufficient area to accommodate a grounded conductor
c. box enclosing the switch is accessible for the installation of an additional or replacement cable without removing finish materials
d. lighting consists of all fluorescent fixtures with integral disconnects for the ballasts
QUESTION 10
-
General-use _____ switches shall be used only to control permanently installed incandescent luminaires unless listed for control of other loads and installed accordingly.
a. dimmerb. timerc. fan speed controld. all of these
QUESTION 11
-
IMC shall be secured _____.
a. any of theseb. within 5 ft of a box or termination fitting when structural members do not readily permit the raceway to be secured within 3 ft of the termina-tionc. except when the IMC is within 3 ft of the service head for an above-the-roof termination of a mastd. by fastening within 3 ft of each outlet box, junction box, device box, cabinet, conduit body, or other conduit termination
QUESTION 12
-
Trade size 1 IMC run straight with threaded couplings shall be supported at intervals not exceeding 12 ft.
True
False
QUESTION 13
-
Where practicable, contact of dissimilar metals shall be avoided in an IMC raceway installation to prevent the possibility of _____.
a. corrosionb. shortsc. none of thesed. galvanic action
QUESTION 14
-
Horizontal runs of IMC supported by openings through framing members at intervals not exceeding 10 ft and securely fastened within 3 ft of terminations shall be permitted.
True
False
QUESTION 15
-
When IMC is cut in the field, reaming is required to remove the burrs and rough edges.
True
False
QUESTION 16
-
Where RMC enters a box, fitting, or other enclosure, _____ shall be provided to protect the wire from abrasion, unless the design of the box, fitting, or enclosure affords equivalent protection.
a. a bushingb. electrical tapec. seal fittingsd. duct seal
QUESTION 17
-
Threadless couplings and connectors used with RMC buried in masonry or concrete shall be the _____ type.
a. raintightb. wet and damp locationc. nonabsorbentd. concrete tight
QUESTION 18
-
Threadless couplings and connectors used with RMC in wet locations shall be _____.
a. nonabsorbentb. weatherproofc. listed for damp locationsd. listed for wet locations
QUESTION 19
-
Galvanized steel, stainless steel and red brass RMC elbows, couplings, and fittings shall be permitted to be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences when protected by _____ approved for the condition.
a. corrosion protectionb. ceramicc. a natural barrierd. backfill
QUESTION 20
-
Aluminum RMC shall be permitted to be installed where approved for the environment.
True
False
QUESTION 21
-
Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, a non-grounding-type receptacle(s) shall be permitted to be replaced with a grounding-type receptacle(s) where supplied through a ground-fault circuit interrupter and _____ shall be marked "GFCI Protected" and "No Equipment Ground," visible after installation.
a. a or bb. their cover platesc. none of thesed. the receptacle(s)
QUESTION 22
-
Receptacle assemblies for installation in countertop surfaces shall be _____ for countertop applications.
a. labeledb. identifiedc. approvedd. listed
QUESTION 23
-
Attachment plugs and cord connectors shall be listed and marked with the _____.
a. amperage ratingb. manufacturer's name or identificationc. voltage ratingd. all of these
QUESTION 24
-
A 125V 15A or 20A receptacle that additionally provides Class 2 power shall be _____ such that the Class 2 circuitry is integral with the receptacle [406.3(F)].
a. listed
b. listed and constructed
c. constructed
d. none of these
QUESTION 25
-
_____, 125V and 250V receptacles installed in a wet location shall have an enclosure that is weatherproof whether or not the attachment plug cap is inserted.
a. a and bb. none of thesec. 20Ad. 15A
QUESTION 26
-
A cable, raceway, or box installed under metal-corrugated sheet roof decking shall be supported so the top of the cable, raceway, or box is not less than _____ in. from the lowest surface of the roof decking to the top of the cable, raceway, or box.
a. 1b. 1 1/2c. 2d. 1/2
QUESTION 27
-
Where cables or nonmetallic raceways are installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is _____ the nearest edge of the wood member.
a. 90º away fromb. not less than 1 1/4 in. fromc. not less than 1/16 in. fromd. immediately adjacent to
QUESTION 28
-
Cables laid in wood notches require protection against nails or screws by using a steel plate at least _____ in. thick, installed before the building finish is applied.
a. 1/2b. 1/4c. 1/8d. 1/16
QUESTION 29
-
Raceways shall be provided with expansion, expansion-deflection, or deflection fittings where necessary to compensate for thermal expansion, deflection, and contraction.
True
False
QUESTION 30
-
Spare or unused raceways shall be sealed with sealants _____ for use with the cable insulation, conductor insulation, bare conductor, shield, or other components.
a. any of theseb. identifiedc. approvedd. listed