Two balanced loads are connected to the a 240kVrms 60Hz line as shown in the figure below. Load 1 draws30kW at a power factor of 0.6 lagging and load 2 draws 45 kVAR at power factor of 0.8 lagging. The real power, reactive power, and magnitude of the line current absorbed by the combined load is close to kW, kVAR, and A. Two balanced loads are connected to the a 240kVrms 60Hz line as shown in the figure below. Load 1 draws 30kW at a power factor of 0.6 lagging kW. and load 2 draws 45KVAR at power factor of 0.8 lagging. The real power absorbed by the combined load is close to Balanced load 1 Balanced load 2

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
icon
Concept explainers
Question
Two balanced loads are connected to the
a 240kVrms60Hz line as shown in the
figure below. Load 1 draws30kW at a
power factor of 0.6 lagging and load 2
draws 45 kVAR at power factor of 0.8
lagging. The real power, reactive power,
and magnitude of the line current
absorbed by the combined load is close to
kW, kVAR, and A.
Two balanced loads are connected to the a 240kVrms 60Hz line as shown in the figure below. Load 1 draws 30kW at a power factor of 0.6 lagging
kW.
and load 2 draws 45KVAR at power factor of 0.8 lagging. The real power absorbed by the combined load is close to
Balanced
load 1
Balanced
load 2
Transcribed Image Text:Two balanced loads are connected to the a 240kVrms60Hz line as shown in the figure below. Load 1 draws30kW at a power factor of 0.6 lagging and load 2 draws 45 kVAR at power factor of 0.8 lagging. The real power, reactive power, and magnitude of the line current absorbed by the combined load is close to kW, kVAR, and A. Two balanced loads are connected to the a 240kVrms 60Hz line as shown in the figure below. Load 1 draws 30kW at a power factor of 0.6 lagging kW. and load 2 draws 45KVAR at power factor of 0.8 lagging. The real power absorbed by the combined load is close to Balanced load 1 Balanced load 2
Expert Solution
steps

Step by step

Solved in 4 steps with 4 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,