The one-line diagram of a power system is shown in the figure below. The 3-ph load is composed of three 4.8-N capacitors in delta connection. The motor draws 50 MW, 0.6 power factor lagging at 20 kV. Use a base of 100 MVA, 20 kV in the generator circuit. Determine the generator and motor internal emfs and the transmission line current. Line M 3-ph Load The three-phase power and line-line ratings are given below: X = 24% X = 6.4% X = 42.35 Q X = 22.5% G:80 MVA 22 kV 22/110 kV 110 kV T1:40 MVA Line: M: 68.85 MVA 20kV The three-phase ratings of the three-winding transformer T2 are: Y-connected 110 kV Primary: Secondary: Tertiary: 40 MVA, 25 MVA, Y-connected 22 kV A-connected 15 MVA, 4.4 kV Neglecting resistance, the leakage impedances are: Zps = 9.6% Zpt = 7.2% Zst = 10% 40 MVA, 40 MVA, 25 MVA, 110 kV 110 kV 22 kV

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
The one-line diagram of a power system is shown in the figure below. The 3-ph load is composed of three 4.8-0 capacitors in delta
connection. The motor draws 50 MW, 0.6 power factor lagging at 20 kV. Use a base of 100 MVA, 20 kV in the generator circuit.
Determine the generator and motor internal emfs and the transmission line current.
Line
M
3-ph Load
The three-phase power and line-line ratings are given below:
X = 24%
22 kV
22/110 kV
G: 80 MVA
T1:40 MVA
X= 6.4%
X= 42.35 Q
X = 22.5%
Line:
110 kV
M: 68.85 MVA
20kV
The three-phase ratings of the three-winding transformer T2 are:
Y-connected
110 kV
Primary:
Secondary:
40 MVA,
Y-connected
25 MVA,
22 kV
Tertiary:
A-connected
15 MVA,
4.4 kV
Neglecting resistance, the leakage impedances are:
110 kV
Zps = 9.6%
Zpt = 7.2%
Zst = 10%
40 MVA,
40 MVA,
25 MVA,
110 kV
22 kV
%3D
Transcribed Image Text:The one-line diagram of a power system is shown in the figure below. The 3-ph load is composed of three 4.8-0 capacitors in delta connection. The motor draws 50 MW, 0.6 power factor lagging at 20 kV. Use a base of 100 MVA, 20 kV in the generator circuit. Determine the generator and motor internal emfs and the transmission line current. Line M 3-ph Load The three-phase power and line-line ratings are given below: X = 24% 22 kV 22/110 kV G: 80 MVA T1:40 MVA X= 6.4% X= 42.35 Q X = 22.5% Line: 110 kV M: 68.85 MVA 20kV The three-phase ratings of the three-winding transformer T2 are: Y-connected 110 kV Primary: Secondary: 40 MVA, Y-connected 25 MVA, 22 kV Tertiary: A-connected 15 MVA, 4.4 kV Neglecting resistance, the leakage impedances are: 110 kV Zps = 9.6% Zpt = 7.2% Zst = 10% 40 MVA, 40 MVA, 25 MVA, 110 kV 22 kV %3D
Expert Solution
steps

Step by step

Solved in 10 steps with 10 images

Blurred answer
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,