The one-line diagram of a power system is shown in the figure below. The 3-ph load is composed of three 4.8-N capacitors in delta connection. The motor draws 50 MW, 0.6 power factor lagging at 20 kV. Use a base of 100 MVA, 20 kV in the generator circuit. Determine the generator and motor internal emfs and the transmission line current. Line M 3-ph Load The three-phase power and line-line ratings are given below: X = 24% X = 6.4% X = 42.35 Q X = 22.5% G:80 MVA 22 kV 22/110 kV 110 kV T1:40 MVA Line: M: 68.85 MVA 20kV The three-phase ratings of the three-winding transformer T2 are: Y-connected 110 kV Primary: Secondary: Tertiary: 40 MVA, 25 MVA, Y-connected 22 kV A-connected 15 MVA, 4.4 kV Neglecting resistance, the leakage impedances are: Zps = 9.6% Zpt = 7.2% Zst = 10% 40 MVA, 40 MVA, 25 MVA, 110 kV 110 kV 22 kV

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
The one-line diagram of a power system is shown in the figure below. The 3-ph load is composed of three 4.8-0 capacitors in delta
connection. The motor draws 50 MW, 0.6 power factor lagging at 20 kV. Use a base of 100 MVA, 20 kV in the generator circuit.
Determine the generator and motor internal emfs and the transmission line current.
Line
M
3-ph Load
The three-phase power and line-line ratings are given below:
X = 24%
22 kV
22/110 kV
G: 80 MVA
T1:40 MVA
X= 6.4%
X= 42.35 Q
X = 22.5%
Line:
110 kV
M: 68.85 MVA
20kV
The three-phase ratings of the three-winding transformer T2 are:
Y-connected
110 kV
Primary:
Secondary:
40 MVA,
Y-connected
25 MVA,
22 kV
Tertiary:
A-connected
15 MVA,
4.4 kV
Neglecting resistance, the leakage impedances are:
110 kV
Zps = 9.6%
Zpt = 7.2%
Zst = 10%
40 MVA,
40 MVA,
25 MVA,
110 kV
22 kV
%3D
Transcribed Image Text:The one-line diagram of a power system is shown in the figure below. The 3-ph load is composed of three 4.8-0 capacitors in delta connection. The motor draws 50 MW, 0.6 power factor lagging at 20 kV. Use a base of 100 MVA, 20 kV in the generator circuit. Determine the generator and motor internal emfs and the transmission line current. Line M 3-ph Load The three-phase power and line-line ratings are given below: X = 24% 22 kV 22/110 kV G: 80 MVA T1:40 MVA X= 6.4% X= 42.35 Q X = 22.5% Line: 110 kV M: 68.85 MVA 20kV The three-phase ratings of the three-winding transformer T2 are: Y-connected 110 kV Primary: Secondary: 40 MVA, Y-connected 25 MVA, 22 kV Tertiary: A-connected 15 MVA, 4.4 kV Neglecting resistance, the leakage impedances are: 110 kV Zps = 9.6% Zpt = 7.2% Zst = 10% 40 MVA, 40 MVA, 25 MVA, 110 kV 22 kV %3D
Expert Solution
steps

Step by step

Solved in 10 steps with 10 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,