The following data were obtained on a 50 kVA 2400/120 V transformer : Open circuit test, instruments on low voltage side: Waltmeter reading = 396 Watts Ammeter reading = 9.65 amperes Voltmeter reading = 120 Volts Short circuit test, instruments on high voltage side: Waltmeter reading = 810 Watts Ammeter reading = 20.8 amperes Voltmeter reading = 92 Volts Find the efficiency when rated kVA is delivered to a load having a power factor of 0.8 lagging. The following data were obtained on a 50 kVA 2400/120 V transformer:

Elements Of Electromagnetics
7th Edition
ISBN:9780190698614
Author:Sadiku, Matthew N. O.
Publisher:Sadiku, Matthew N. O.
ChapterMA: Math Assessment
Section: Chapter Questions
Problem 1.1MA
icon
Related questions
Question
The following data were obtained on a 50 kVA 2400/120 V transformer:
Open circuit test, instruments on low voltage side:
Waltmeter reading = 396 Watts
Ammeter reading = 9.65 amperes
Voltmeter reading = 120 Volts
Short circuit test, instruments on high voltage side:
Waltmeter reading = 810 Watts
Ammeter reading = 20.8 amperes
Voltmeter reading = 92 Volts
Find the efficiency when rated kVA is delivered to a load having a power
factor of 0.8 lagging.The following data were obtained on a 50 kVA 2400/120 V transformer :
Open circuit test, instruments on low voltage side:
Waltmeter reading = 396 Watts
Ammeter reading = 9.65 amperes
Voltmeter reading = 120 Volts
Short circuit test, instruments on high voltage side:
Waltmeter reading = 810 Watts
Ammeter reading = 20.8 amperes
Voltmeter reading = 92 Volts
Find the efficiency when rated kVA is delivered to a load having a power
factor of 0.8 lagging.
Transcribed Image Text:The following data were obtained on a 50 kVA 2400/120 V transformer: Open circuit test, instruments on low voltage side: Waltmeter reading = 396 Watts Ammeter reading = 9.65 amperes Voltmeter reading = 120 Volts Short circuit test, instruments on high voltage side: Waltmeter reading = 810 Watts Ammeter reading = 20.8 amperes Voltmeter reading = 92 Volts Find the efficiency when rated kVA is delivered to a load having a power factor of 0.8 lagging.The following data were obtained on a 50 kVA 2400/120 V transformer : Open circuit test, instruments on low voltage side: Waltmeter reading = 396 Watts Ammeter reading = 9.65 amperes Voltmeter reading = 120 Volts Short circuit test, instruments on high voltage side: Waltmeter reading = 810 Watts Ammeter reading = 20.8 amperes Voltmeter reading = 92 Volts Find the efficiency when rated kVA is delivered to a load having a power factor of 0.8 lagging.
Expert Solution
steps

Step by step

Solved in 2 steps with 1 images

Blurred answer
Knowledge Booster
Conduction
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Elements Of Electromagnetics
Elements Of Electromagnetics
Mechanical Engineering
ISBN:
9780190698614
Author:
Sadiku, Matthew N. O.
Publisher:
Oxford University Press
Mechanics of Materials (10th Edition)
Mechanics of Materials (10th Edition)
Mechanical Engineering
ISBN:
9780134319650
Author:
Russell C. Hibbeler
Publisher:
PEARSON
Thermodynamics: An Engineering Approach
Thermodynamics: An Engineering Approach
Mechanical Engineering
ISBN:
9781259822674
Author:
Yunus A. Cengel Dr., Michael A. Boles
Publisher:
McGraw-Hill Education
Control Systems Engineering
Control Systems Engineering
Mechanical Engineering
ISBN:
9781118170519
Author:
Norman S. Nise
Publisher:
WILEY
Mechanics of Materials (MindTap Course List)
Mechanics of Materials (MindTap Course List)
Mechanical Engineering
ISBN:
9781337093347
Author:
Barry J. Goodno, James M. Gere
Publisher:
Cengage Learning
Engineering Mechanics: Statics
Engineering Mechanics: Statics
Mechanical Engineering
ISBN:
9781118807330
Author:
James L. Meriam, L. G. Kraige, J. N. Bolton
Publisher:
WILEY