The air in a 6 m x 5 m x 4 m hospital room is to be completely replaced by conditioned air every 20 min. If the average air velocity in the circular air duct leading to the room is no to exceed 5 m/s, determine the minimum diameter of the duct. a.0.16 m-diameter b.0.64 m-diameter c.0.32 m-diameter d.0.08 m-diameter

Refrigeration and Air Conditioning Technology (MindTap Course List)
8th Edition
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Chapter37: Air Distribution And Balance
Section: Chapter Questions
Problem 8RQ
icon
Related questions
icon
Concept explainers
Question
The air in a 6 m x 5 m x 4 m hospital room is to be completely replaced by conditioned air every 20 min. If the average air velocity in the circular air duct leading to the room is no to exceed 5 m/s, determine the minimum diameter of the duct.
a.0.16 m-diameter
b.0.64 m-diameter
c.0.32 m-diameter
d.0.08 m-diameter
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Hydronics
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Refrigeration and Air Conditioning Technology (Mi…
Refrigeration and Air Conditioning Technology (Mi…
Mechanical Engineering
ISBN:
9781305578296
Author:
John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:
Cengage Learning
Principles of Heat Transfer (Activate Learning wi…
Principles of Heat Transfer (Activate Learning wi…
Mechanical Engineering
ISBN:
9781305387102
Author:
Kreith, Frank; Manglik, Raj M.
Publisher:
Cengage Learning