O a. S- S0mm? & %VD = 2.99%

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
Consider the below secondary system
MV.CBD
Primary
DT
200KVA
20KV-220/380V
LV.CB
Outdoor temperature t=40°c
Secondary main
XLPE
direct in air
L-AB=150m
FACTORY BUILDING
Indoor temperature t=30 C
SD1 C
30
E SD3
30
B
L-BE=100m
On cable tray
50KW
L-BC=60m
50KVA
in conduit
PVC
XLPE
L-BD-40m
in duct
XLPE
SD2
30
D
50HP
where all loads are lagging with PF=0.8. The table of conductor parameters is as follow
Conductor size
16 mm2
25 mm2
35 mm2
Ampacity / phase
R (N /km)
X (Q /km)
50A
0.7
0.07
63A
0.6
0.06
80A
0.5
0.05
50 mm2
100A
0.4
0.04
70 mm2
140A
0.3
0.03
95 mm2
180A
0.2
0.02
120 mm2
150 mm2
250A
0.1
0.01
350A
0.09
0.009
Assuming that correction factor K=0.7 for all loads. From B to E, the size of cable per phase (S) and the percentage voltage drop (%VD) will
be:
Select one:
O a. S= 50mm? & %VD = 2.99%
Ob. S= 70mm? & %VD = 1.199%
Oc. S= 95mm? & %VD = 1.99%
O d. None of these
O e. S= 95mm? & %VD = 0.93%
O f. S= 70mm? & %VD = 0.99%
Transcribed Image Text:Consider the below secondary system MV.CBD Primary DT 200KVA 20KV-220/380V LV.CB Outdoor temperature t=40°c Secondary main XLPE direct in air L-AB=150m FACTORY BUILDING Indoor temperature t=30 C SD1 C 30 E SD3 30 B L-BE=100m On cable tray 50KW L-BC=60m 50KVA in conduit PVC XLPE L-BD-40m in duct XLPE SD2 30 D 50HP where all loads are lagging with PF=0.8. The table of conductor parameters is as follow Conductor size 16 mm2 25 mm2 35 mm2 Ampacity / phase R (N /km) X (Q /km) 50A 0.7 0.07 63A 0.6 0.06 80A 0.5 0.05 50 mm2 100A 0.4 0.04 70 mm2 140A 0.3 0.03 95 mm2 180A 0.2 0.02 120 mm2 150 mm2 250A 0.1 0.01 350A 0.09 0.009 Assuming that correction factor K=0.7 for all loads. From B to E, the size of cable per phase (S) and the percentage voltage drop (%VD) will be: Select one: O a. S= 50mm? & %VD = 2.99% Ob. S= 70mm? & %VD = 1.199% Oc. S= 95mm? & %VD = 1.99% O d. None of these O e. S= 95mm? & %VD = 0.93% O f. S= 70mm? & %VD = 0.99%
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Operational amplifier
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,