Example 8.4 The one line diagram of a simple three-bus power system is shown in the figure. Each generator is j0.1 j0.2 represented by an emf behind the transient reactance. All impedances are expressed in per unit j0.1 j0.2 in a common 100 MVA base, and for simplicity, j0.8 resistances are neglected. The following assumption 2 are made: j0.4 j0.4 •shunt capacitances are neglected and the system is considered on no load. •all generators are running at their rated voltage 3 and rated frequency with their emf in phase Determine the fault current, the bus voltages and the line currents during the fault when a balanced three-phase fault with a fault impedance Z; = j0.16 %3D p.u. fault occurs on bus 3

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.9P
icon
Related questions
Question
Example 8.4
The one line diagram of a simple three-bus
power
system is shown in the figure. Each generator is
j0.1
j0.2
represented by an emf behind the transient
reactance. All impedances are expressed in per unit
j0.1
j0.2
in a common 100 MVA base, and for simplicity,
j0.8
resistances are neglected. The following assumption
2
are made:
j0.4
j0.4
•shunt capacitances are neglected and the system
is considered on no load.
•all generators are running at their rated voltage
3
and rated frequency with their emf in phase
Determine the fault current, the bus voltages and
the line currents during the fault when a balanced
three-phase fault with a fault impedance Z; = j0.16
%3D
p.u. fault occurs on bus 3
Transcribed Image Text:Example 8.4 The one line diagram of a simple three-bus power system is shown in the figure. Each generator is j0.1 j0.2 represented by an emf behind the transient reactance. All impedances are expressed in per unit j0.1 j0.2 in a common 100 MVA base, and for simplicity, j0.8 resistances are neglected. The following assumption 2 are made: j0.4 j0.4 •shunt capacitances are neglected and the system is considered on no load. •all generators are running at their rated voltage 3 and rated frequency with their emf in phase Determine the fault current, the bus voltages and the line currents during the fault when a balanced three-phase fault with a fault impedance Z; = j0.16 %3D p.u. fault occurs on bus 3
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Economic load dispatch
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning