controller that the Given a proportional controlled variable is a process temperature with a range of 50°C (Tmin)to 100°C (Tmax), set-point, SP of 75°C and proportional gain Kp of 0.5. Under normal condition, the set-point is maintained with an controller output, po of 50%. If a load change which requires a 60% controller output, p occurs, determine the proportional offset error, ep and measure temperature, T. Hint: ep-p-pokp; T=SP-ep(Tmax-Tmin)100 please provide answer

icon
Related questions
Question
Given a proportional controller that the
controlled variable is a process
temperature with a range of 50°C
(Tmin)to 100°C (Tmax), set-point, SP of
75°C and proportional gain Kp of 0.5.
Under normal condition, the set-point is
maintained with an controller output, po
of 50%. If a load change which requires a
60% controller output, p occurs,
determine the proportional offset error, ep
and measure temperature, T. Hint:
ep-p-pokp; T=SP-ep(Tmax-Tmin)100
please provide answer
Transcribed Image Text:Given a proportional controller that the controlled variable is a process temperature with a range of 50°C (Tmin)to 100°C (Tmax), set-point, SP of 75°C and proportional gain Kp of 0.5. Under normal condition, the set-point is maintained with an controller output, po of 50%. If a load change which requires a 60% controller output, p occurs, determine the proportional offset error, ep and measure temperature, T. Hint: ep-p-pokp; T=SP-ep(Tmax-Tmin)100 please provide answer