a) What is the minimum required transformer rating in kVA? b) By what percentage could the required transformer rating be reduced if a capacitor bank were installed in parallel with the motors, improving the power factor of the loadcentre to unity?

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question

a) What is the minimum required transformer rating in kVA?
b) By what percentage could the required transformer rating be reduced if a
capacitor bank were installed in parallel with the motors, improving the power
factor of the loadcentre to unity? 

1. Consider the three-phase loadcentre shown below:
13.8 KVRMS
600 VEMS
(M
(M)
(M)
M
Motor 1
Motor 2
Motor 3
Motor 4
80 hp
80 hp
80 hp
80 hp
Transcribed Image Text:1. Consider the three-phase loadcentre shown below: 13.8 KVRMS 600 VEMS (M (M) (M) M Motor 1 Motor 2 Motor 3 Motor 4 80 hp 80 hp 80 hp 80 hp
Each motor is rated at 80 hp but is only loaded mechanically as follows:
Motor #
% Loading
1
50
2
70
3
20
4
90
The relationship between % of full load for each motor and efficiency (they are all
the same) is given by the graph below:
120
100
80
60
40
20
20
40
60
80
100
120
Motor Loading (96)
The relationship between % of full load for each motor and power factor (they are
all the same) is given by the graph below:
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
20
40
60
80
100
120
Motor Loading (96)
pf (lagging)
Eiciency (%)
Transcribed Image Text:Each motor is rated at 80 hp but is only loaded mechanically as follows: Motor # % Loading 1 50 2 70 3 20 4 90 The relationship between % of full load for each motor and efficiency (they are all the same) is given by the graph below: 120 100 80 60 40 20 20 40 60 80 100 120 Motor Loading (96) The relationship between % of full load for each motor and power factor (they are all the same) is given by the graph below: 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 20 40 60 80 100 120 Motor Loading (96) pf (lagging) Eiciency (%)
Expert Solution
steps

Step by step

Solved in 7 steps with 4 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,