a) The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a 1000-MVA, 500-kV base in the zone of line 1-2. Neglect the A-Y transformer phase shifts.
a) The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence reactance diagrams using a 1000-MVA, 500-kV base in the zone of line 1-2. Neglect the A-Y transformer phase shifts.
Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
Related questions
Question
Just need drawing of zero, positive, and negative sequence in part A
![The single-line diagram of a three-phase power system is shown in below Figure.
Equipment ratings are given as follows:
Synchronous generators:
1000 MVA
1000 MVA
500 MVA
750 MVA
GI
G2
G3
G4
Transformers:
TI
T2
T3
T4
1000 MVA
1000 MVA
500 MVA
750 MVA
Transmission lines:
500 kV
500 kV
500 kV
1-2
1-3
2-3
a)
b)
c)
d)
15 kV
15 kV
13.8 kV
13.8 kV
Xd = X2= 0.18, Xo = 0.07 per unit
Xd = X2=0.20, Xo = 0.10 per unit
Xd = X2= 0.15, Xo = 0.05 per unit
Xd 0.30, X₂=0.40, Xo = 0.10 per unit
15 kV A/500 kV Y
15 kV A/500 kV Y
15 kV Y/500 kV Y
15 kV Y/500 kV Y
X = 0.10 per unit
X= 0.10 per unit
X = 0.12 per unit
X=0.11 per unit
Χρ = 50 Ω, Χ@ = 150 Ω
X₁40 S2, Xo= 100 2
X₁40 2, Xo 100 2
The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit
using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence
reactance diagrams using a 1000-MVA, 500-kV base in the zone of line 1-2. Neglect
the A-Y transformer phase shifts.
Faults at bus 1 are of interest. Determine the Thévenin equivalent of each
sequence network as viewed from the fault bus 1. Prefault voltage is 1.0 per unit.
Prefault load currents and A-Y transformer phase shifts are neglected. (Hint: Use the
Y-A conversion.)
Determine the subtransient fault current in per-unit and in kA during a bolted
three-phase fault at the fault bus 1.
Determine the subtransient fault current in per-unit and in kA, as well as the
per-unit line-to-ground voltages at the fault bus for a bolted single line-to-ground
fault at the fault bus 1.](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F4bf62d6d-db44-481f-809c-2b5fe2fdf00c%2Fcaf28d85-1b31-47c1-a293-57176eaea231%2Fhqo3u7a_processed.png&w=3840&q=75)
Transcribed Image Text:The single-line diagram of a three-phase power system is shown in below Figure.
Equipment ratings are given as follows:
Synchronous generators:
1000 MVA
1000 MVA
500 MVA
750 MVA
GI
G2
G3
G4
Transformers:
TI
T2
T3
T4
1000 MVA
1000 MVA
500 MVA
750 MVA
Transmission lines:
500 kV
500 kV
500 kV
1-2
1-3
2-3
a)
b)
c)
d)
15 kV
15 kV
13.8 kV
13.8 kV
Xd = X2= 0.18, Xo = 0.07 per unit
Xd = X2=0.20, Xo = 0.10 per unit
Xd = X2= 0.15, Xo = 0.05 per unit
Xd 0.30, X₂=0.40, Xo = 0.10 per unit
15 kV A/500 kV Y
15 kV A/500 kV Y
15 kV Y/500 kV Y
15 kV Y/500 kV Y
X = 0.10 per unit
X= 0.10 per unit
X = 0.12 per unit
X=0.11 per unit
Χρ = 50 Ω, Χ@ = 150 Ω
X₁40 S2, Xo= 100 2
X₁40 2, Xo 100 2
The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit
using generator 3 ratings as a base. Draw the zero-, positive-, and negative-sequence
reactance diagrams using a 1000-MVA, 500-kV base in the zone of line 1-2. Neglect
the A-Y transformer phase shifts.
Faults at bus 1 are of interest. Determine the Thévenin equivalent of each
sequence network as viewed from the fault bus 1. Prefault voltage is 1.0 per unit.
Prefault load currents and A-Y transformer phase shifts are neglected. (Hint: Use the
Y-A conversion.)
Determine the subtransient fault current in per-unit and in kA during a bolted
three-phase fault at the fault bus 1.
Determine the subtransient fault current in per-unit and in kA, as well as the
per-unit line-to-ground voltages at the fault bus for a bolted single line-to-ground
fault at the fault bus 1.
![Line 1-2
Line 1-3
2
2
T₂
Line 2-3
3
T3
38
TA
38
21 Ý
3
4
youthiy](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F4bf62d6d-db44-481f-809c-2b5fe2fdf00c%2Fcaf28d85-1b31-47c1-a293-57176eaea231%2Fbhcmfbt_processed.png&w=3840&q=75)
Transcribed Image Text:Line 1-2
Line 1-3
2
2
T₂
Line 2-3
3
T3
38
TA
38
21 Ý
3
4
youthiy
Expert Solution
![](/static/compass_v2/shared-icons/check-mark.png)
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 8 steps with 3 images
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
![Fundamentals of Electric Circuits](https://www.bartleby.com/isbn_cover_images/9780078028229/9780078028229_smallCoverImage.gif)
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
![Electric Circuits. (11th Edition)](https://www.bartleby.com/isbn_cover_images/9780134746968/9780134746968_smallCoverImage.gif)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
![Engineering Electromagnetics](https://www.bartleby.com/isbn_cover_images/9780078028151/9780078028151_smallCoverImage.gif)
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,