A single line diagram of a power system is shown in Fig.3.1. All the sequence reactances of the power system components are depicted in per unit on 20 MVA base, 110KV (L-L) in transmission circuit. If a single line to ground fault occurs on phase a through a reactance of 150 ohm at F, determine the current in ampere fed into the fault. The fault point F is assumed to be at 65% of transmission line length from the bus bar connected to generators A and B. 20 MVA A Xe-Xpj 0.1 X-j 0.35 11 KV C X-j0.3 X=j0.3 X=j0.05/ 110 KV 20 MVA X-X,-X-J 0.1 X=X,=X;=j 0.1 Transmission circuit X,=j0.25 X;=j0.25 X-j0.05 Y D |Xx=X;= j 0.1 X;~j 0.35 X-X-X;-J 0.1 X-X;=X;=j 0.1

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
Please solve step by step subject power system analysis
A single line diagram of a power system is shown in Fig.3.1. All the
sequence reactances of the power system components are depicted in per
unit on 20 MVA base, 110KV (L-L) in transmission circuit. If a single line
to ground fault occurs on phase a through a reactance of 150 ohm at F,
determine the current in ampere fed into the fault. The fault point F is
assumed to be at 65% of transmission line length from the bus bar
connected to generators A and B.
20 MVA
X-X-j 0.1 X-j 0.35
ntn 11 KV
A
X,-j0.3
X=j0.3
X=j0.05
C
110 KV
20 MVA
X-X-X;-J 0.1
X=X=X=j 0.1
X=j0.25
Xx=j0.25
Xo=j0.05
Transmission
circuit
CY
Y
B
D
|X=Xy=j 0.1 X;-j 0.35
X-X,-X3-J 0.1
X-X,=X;=j 0.1
Transcribed Image Text:A single line diagram of a power system is shown in Fig.3.1. All the sequence reactances of the power system components are depicted in per unit on 20 MVA base, 110KV (L-L) in transmission circuit. If a single line to ground fault occurs on phase a through a reactance of 150 ohm at F, determine the current in ampere fed into the fault. The fault point F is assumed to be at 65% of transmission line length from the bus bar connected to generators A and B. 20 MVA X-X-j 0.1 X-j 0.35 ntn 11 KV A X,-j0.3 X=j0.3 X=j0.05 C 110 KV 20 MVA X-X-X;-J 0.1 X=X=X=j 0.1 X=j0.25 Xx=j0.25 Xo=j0.05 Transmission circuit CY Y B D |X=Xy=j 0.1 X;-j 0.35 X-X,-X3-J 0.1 X-X,=X;=j 0.1
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 11 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,