A single line diagram of a power system is shown in Fig.3.1. All the sequence reactances of the power system components are depicted in per unit on 20 MVA base, 110KV (L-L) in transmission circuit. If a single line to ground fault occurs on phase a through a reactance of 150 ohm at F, determine the current in ampere fed into the fault. The fault point F is assumed to be at 65% of transmission line length from the bus bar connected to generators A and B. 20 MVA A Xe-Xpj 0.1 X-j 0.35 11 KV C X-j0.3 X=j0.3 X=j0.05/ 110 KV 20 MVA X-X,-X-J 0.1 X=X,=X;=j 0.1 Transmission circuit X,=j0.25 X;=j0.25 X-j0.05 Y D |Xx=X;= j 0.1 X;~j 0.35 X-X-X;-J 0.1 X-X;=X;=j 0.1

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.49P: Consider the single-Line diagram of a power system shown in Figure 3.42 with equipment ratings...
icon
Related questions
Question
Please solve step by step subject power system analysis
A single line diagram of a power system is shown in Fig.3.1. All the
sequence reactances of the power system components are depicted in per
unit on 20 MVA base, 110KV (L-L) in transmission circuit. If a single line
to ground fault occurs on phase a through a reactance of 150 ohm at F,
determine the current in ampere fed into the fault. The fault point F is
assumed to be at 65% of transmission line length from the bus bar
connected to generators A and B.
20 MVA
X-X-j 0.1 X-j 0.35
ntn 11 KV
A
X,-j0.3
X=j0.3
X=j0.05
C
110 KV
20 MVA
X-X-X;-J 0.1
X=X=X=j 0.1
X=j0.25
Xx=j0.25
Xo=j0.05
Transmission
circuit
CY
Y
B
D
|X=Xy=j 0.1 X;-j 0.35
X-X,-X3-J 0.1
X-X,=X;=j 0.1
Transcribed Image Text:A single line diagram of a power system is shown in Fig.3.1. All the sequence reactances of the power system components are depicted in per unit on 20 MVA base, 110KV (L-L) in transmission circuit. If a single line to ground fault occurs on phase a through a reactance of 150 ohm at F, determine the current in ampere fed into the fault. The fault point F is assumed to be at 65% of transmission line length from the bus bar connected to generators A and B. 20 MVA X-X-j 0.1 X-j 0.35 ntn 11 KV A X,-j0.3 X=j0.3 X=j0.05 C 110 KV 20 MVA X-X-X;-J 0.1 X=X=X=j 0.1 X=j0.25 Xx=j0.25 Xo=j0.05 Transmission circuit CY Y B D |X=Xy=j 0.1 X;-j 0.35 X-X,-X3-J 0.1 X-X,=X;=j 0.1
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 5 steps with 11 images

Blurred answer
Knowledge Booster
Stability Analysis in Power System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning