A new building is being construct and linear measurement of two bays shown in table 1.0. Вay Measured Length Temperature (°C) Tension (N) 1 21.367 30 163 35.648 29 170 The 30 m steel tape was used in this measurement having mass of 0.30 N/m and a cross-sectional area of 4.00mm?. It was standardized on the flat at 25°c under a pull of 120 N. The coefficient of linear expansion for the steel tape is 1.7 x 10-5/°c and Young's modulus is 20.0 x 104 MN/m2. Determine the absolute length of this survey line. (P- Ps) EL Tension Correction D %3D AE w'YL 24 P2 Sagging Correction = %3D Temperature Correction aL (t-t.) 5.

Structural Analysis
6th Edition
ISBN:9781337630931
Author:KASSIMALI, Aslam.
Publisher:KASSIMALI, Aslam.
Chapter2: Loads On Structures
Section: Chapter Questions
Problem 1P
icon
Related questions
Question
100%
Normal
No Spacing
Heading 1
Heading 2
Styles
Pane
Dictate
Editor
Crea
5.
A new building is being construct and linear measurement of two bays shown in
table 1.0.
Вay
Measured Length
Temperature (C)
Tension (N)
1
21.367
30
163
2
35.648
29
170
The 30 m steel tape was used in this measurement having mass of 0.30 N/m and a
cross-sectional area of 4.00mm². It was standardized on the flat at 25°c under a
pull of 120 N. The coefficient of linear expansion for the steel tape is 1.7 x 10-5/°c
and Young's modulus is 20.0 x 101 MN/m2. Determine the absolute length of this
survey line.
(P- Ps) EL
Tension Correction =
AE
3
Sagging Correction =
%3D
24 P2
Temperature Correction
aL (t-t.)
Transcribed Image Text:Normal No Spacing Heading 1 Heading 2 Styles Pane Dictate Editor Crea 5. A new building is being construct and linear measurement of two bays shown in table 1.0. Вay Measured Length Temperature (C) Tension (N) 1 21.367 30 163 2 35.648 29 170 The 30 m steel tape was used in this measurement having mass of 0.30 N/m and a cross-sectional area of 4.00mm². It was standardized on the flat at 25°c under a pull of 120 N. The coefficient of linear expansion for the steel tape is 1.7 x 10-5/°c and Young's modulus is 20.0 x 101 MN/m2. Determine the absolute length of this survey line. (P- Ps) EL Tension Correction = AE 3 Sagging Correction = %3D 24 P2 Temperature Correction aL (t-t.)
Expert Solution
steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Braced cuts
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, civil-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Structural Analysis
Structural Analysis
Civil Engineering
ISBN:
9781337630931
Author:
KASSIMALI, Aslam.
Publisher:
Cengage,
Structural Analysis (10th Edition)
Structural Analysis (10th Edition)
Civil Engineering
ISBN:
9780134610672
Author:
Russell C. Hibbeler
Publisher:
PEARSON
Principles of Foundation Engineering (MindTap Cou…
Principles of Foundation Engineering (MindTap Cou…
Civil Engineering
ISBN:
9781337705028
Author:
Braja M. Das, Nagaratnam Sivakugan
Publisher:
Cengage Learning
Fundamentals of Structural Analysis
Fundamentals of Structural Analysis
Civil Engineering
ISBN:
9780073398006
Author:
Kenneth M. Leet Emeritus, Chia-Ming Uang, Joel Lanning
Publisher:
McGraw-Hill Education
Sustainable Energy
Sustainable Energy
Civil Engineering
ISBN:
9781337551663
Author:
DUNLAP, Richard A.
Publisher:
Cengage,
Traffic and Highway Engineering
Traffic and Highway Engineering
Civil Engineering
ISBN:
9781305156241
Author:
Garber, Nicholas J.
Publisher:
Cengage Learning