A d.c. shunt motor after running for several hours on constant voltage mains at 400 V takes a field current of 1.6 A. If the temperature rise is known to be 40°C, what value of extra circuit resistance is required to adjust the field current to 1.6 A when starting from cold at 20°C? Temperature coefficient = 0.0043/°C at 20°C. [36.69 0]
A d.c. shunt motor after running for several hours on constant voltage mains at 400 V takes a field current of 1.6 A. If the temperature rise is known to be 40°C, what value of extra circuit resistance is required to adjust the field current to 1.6 A when starting from cold at 20°C? Temperature coefficient = 0.0043/°C at 20°C. [36.69 0]