A balanced Y-connected load absorbs in total 3 kw at a power factor of 0.6 lagging. If the line voitage at the load terminal is 500 V, then the magnitude of the line current is equal to: Select one: O a. 2.32 A O b. 5.76 A O C. 332 A O d. 33.2 A

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter2: Fundamentals
Section: Chapter Questions
Problem 2.45P: Two balanced Y-connected loads, one drawing 10 kW at 0.8 power factor lagging and the other IS kW at...
icon
Related questions
Question
100%
A balanced Y-connected load absorbs in total 3 kw at a power factor of 0.6 lagging. If the line voltage at the load terminal is 500 V, then
the magnitude of the line current is equal to:
Select one:
O a. 2.32 A
O b.5.76 A
O C. 332 A
O d. 33.2 A
Transcribed Image Text:A balanced Y-connected load absorbs in total 3 kw at a power factor of 0.6 lagging. If the line voltage at the load terminal is 500 V, then the magnitude of the line current is equal to: Select one: O a. 2.32 A O b.5.76 A O C. 332 A O d. 33.2 A
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Compensation Techniques in Transmission Line
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning