A 50 kVA, 500 V, single phase alternator gives 700 V on open circuit at the field current of 15 A. While on short circuit a short current of 375 flows for the same field current. Assuming the armature resistance of 0.8 ohm, calculate (1) Synchronous impedance and (2) synchronous reactance
Synchronous Generator
In comparison to an asynchronous generator, it is a machine where the rotor speed is equal to the rotating magnetic field produced by the stator, i.e., mechanical speed is equal to the electrical speed, thus called synchronous, and not asynchronous.
Salient Pole Rotor
Salient pole rotor includes a large number of exposed poles mounted on a magnetic wheel. The construction of a bright pole is as shown in the image on the left. The proposed poles are made of metal laminations. The rotor winding is provided on these poles and is supported by pole shoes.
A 50 kVA, 500 V, single phase alternator gives 700 V on open circuit at the field current of 15 A. While on short circuit a short current of 375 flows for the same field current. Assuming the armature resistance of 0.8 ohm, calculate
(1) Synchronous impedance and
(2) synchronous reactance
Step by step
Solved in 2 steps with 2 images