A 3-phase, 30 MVA, 33 kV alternator has internal reactance of 4% and negligible resistance. Find the external reactance per phase to be connected in series with the alternator so that steady current on shortcircuit does not exceed 10 times the full load current. [2·178 Ω

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question

A 3-phase, 30 MVA, 33 kV alternator has internal reactance of 4% and negligible resistance. Find the
external reactance per phase to be connected in series with the alternator so that steady current on shortcircuit does not exceed 10 times the full load current. [2·178 Ω]

TUTORIAL PROBLEMS
1. A 3-phase, 30 MVA, 33 kV alternator has internal reactance of 4% and negligible resistance. Find the
external reactance per phase to be connected in series with the alternator so that steady current on short-
circuit does not exceed 10 times the full load current.
[2-178 Q|
2. A 3-phase transmission line operating at 33 kV and having a resistance of 5 and reactance of 20Q is
connected to the generating station through 15,000 kVA step-up transformer. Connected to the bus-bar
are two alternators, one of 10,000 kVA with 10% reactance and another of 5000 kVA with 7-5% reac-
tance. Calculate the short-circuit kVA fed to the symmetrical fault between phases if it occurs
(i) at the load end of transmission line
(ii) at the high voltage terminals of the transformer
|(1) 44,500 kVA (ii) 100,000 kVA]
3. The plant capacity of a 3-phase generating station consists of two 8 MVA generators of reactance 14-5%
each and one 4 MVA generator of reactance 9-5%. These are connected to a common bus-bar from
which loads are taken through a number of 3 MVA step-up transformers each having 4% reactance.
Determine the MVA rating of the circuit breakers on (i) L.V. side and (ii) H.V. side. Reactances given
|(1) 15-24 MVA (ii) 50-25 MVA]
are based on the MVA of each equipment.
4. The 33 kV bus-bar of a station are in two sections A and B separated by a reactor. Section A is fed from
four 10 MVA generators each having 20% reactance and section B is fed from the grid through 50 MVA
transformer of 10% reactance. The circuit breakers have rupturing capacity of 500 MVA. Find the
reactance of the reactor to prevent the circuit breakers being overloaded if a symmetrical short-circuit
occurs on an outgoing feeder connected to it.
5. A generating station has five section bus-bar connected with a tie-bar through 7-5% reactors rated at
3000 kVA. Each generator is of 3000 kVA with 10% reactance and is connected to one section of the
bus-bar. Find the total steady input to a dead short-circuit between the lines on one of the sections of the
bus-bars (i) with and (ii) without reactors.
[1-45 Q|
|() 55-3 MVA (ii) 150 MVA]
6. A generating station has four bus-bar sections. Each section is connected to tie-bar though 20% reactors
rated at 200 MVA. Generators of total capacity 100 MVA and 20% reactance are connected to each bus-
bar section. Calculate the MVA fed to a fault under short-circuit condition one one of the bus-bars.
[1000 MVA]
Transcribed Image Text:TUTORIAL PROBLEMS 1. A 3-phase, 30 MVA, 33 kV alternator has internal reactance of 4% and negligible resistance. Find the external reactance per phase to be connected in series with the alternator so that steady current on short- circuit does not exceed 10 times the full load current. [2-178 Q| 2. A 3-phase transmission line operating at 33 kV and having a resistance of 5 and reactance of 20Q is connected to the generating station through 15,000 kVA step-up transformer. Connected to the bus-bar are two alternators, one of 10,000 kVA with 10% reactance and another of 5000 kVA with 7-5% reac- tance. Calculate the short-circuit kVA fed to the symmetrical fault between phases if it occurs (i) at the load end of transmission line (ii) at the high voltage terminals of the transformer |(1) 44,500 kVA (ii) 100,000 kVA] 3. The plant capacity of a 3-phase generating station consists of two 8 MVA generators of reactance 14-5% each and one 4 MVA generator of reactance 9-5%. These are connected to a common bus-bar from which loads are taken through a number of 3 MVA step-up transformers each having 4% reactance. Determine the MVA rating of the circuit breakers on (i) L.V. side and (ii) H.V. side. Reactances given |(1) 15-24 MVA (ii) 50-25 MVA] are based on the MVA of each equipment. 4. The 33 kV bus-bar of a station are in two sections A and B separated by a reactor. Section A is fed from four 10 MVA generators each having 20% reactance and section B is fed from the grid through 50 MVA transformer of 10% reactance. The circuit breakers have rupturing capacity of 500 MVA. Find the reactance of the reactor to prevent the circuit breakers being overloaded if a symmetrical short-circuit occurs on an outgoing feeder connected to it. 5. A generating station has five section bus-bar connected with a tie-bar through 7-5% reactors rated at 3000 kVA. Each generator is of 3000 kVA with 10% reactance and is connected to one section of the bus-bar. Find the total steady input to a dead short-circuit between the lines on one of the sections of the bus-bars (i) with and (ii) without reactors. [1-45 Q| |() 55-3 MVA (ii) 150 MVA] 6. A generating station has four bus-bar sections. Each section is connected to tie-bar though 20% reactors rated at 200 MVA. Generators of total capacity 100 MVA and 20% reactance are connected to each bus- bar section. Calculate the MVA fed to a fault under short-circuit condition one one of the bus-bars. [1000 MVA]
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,