500 KW loading power factor 0.6 is lagging. The combined power factor 0.9 is to be used by the over-expeded Synchronus Motor. If the Synchronus motor is taking 80 kw. 1. Synchronus motor's power factor 2. Synchronus motor leaping KVAR 3. Find the KVA of the Synchronus Motor.
Synchronous Generator
In comparison to an asynchronous generator, it is a machine where the rotor speed is equal to the rotating magnetic field produced by the stator, i.e., mechanical speed is equal to the electrical speed, thus called synchronous, and not asynchronous.
Salient Pole Rotor
Salient pole rotor includes a large number of exposed poles mounted on a magnetic wheel. The construction of a bright pole is as shown in the image on the left. The proposed poles are made of metal laminations. The rotor winding is provided on these poles and is supported by pole shoes.
500 KW loading power factor 0.6 is lagging. The combined power factor 0.9 is to be used by the over-expeded Synchronus Motor. If the Synchronus motor is taking 80 kw. 1. Synchronus motor's power factor 2. Synchronus motor leaping KVAR 3. Find the KVA of the Synchronus Motor.
Step by step
Solved in 2 steps with 2 images