3.5 Consider the microgrid of Figure 3.68. A three-phase 500 kVA, 440 V Y grounded/3.2 kV delta transformer T, with the per unit reactance of AC bus Local loads 250 kVA DC bus PV generating station DC/AC Inverter m Zyans Local power grid 3.2 kv T2 13.2 KV 440 V/3.2 kV 500 kVA 3.5% 3.2/13.2 kV 500 KVA, 8% Figure 3.68 A one-line diagram of Problem 3.5. PROBLEMS 173 3.5% feeds from an AC source of a PV generating station. The distribu- tion line is 10 miles long and has a series impedance of 0.01 + j0.09 2 per mile. The local load is 250 kVA. The balance of power can be injected into the local utility using a 500 kVA, 3.2 kV Y grounded/13.2 kV delta transformer T2 with the per unit reactance of 8%. Assume the voltage base of 13.8 kV on the local power grid side, kVA base of 500, and the DC bus voltage of 800 V. Compute the following: (i) The inverter and the PV generating station ratings. (ii) The per unit impedance diagram of the microgrid.
3.5 Consider the microgrid of Figure 3.68. A three-phase 500 kVA, 440 V Y grounded/3.2 kV delta transformer T, with the per unit reactance of AC bus Local loads 250 kVA DC bus PV generating station DC/AC Inverter m Zyans Local power grid 3.2 kv T2 13.2 KV 440 V/3.2 kV 500 kVA 3.5% 3.2/13.2 kV 500 KVA, 8% Figure 3.68 A one-line diagram of Problem 3.5. PROBLEMS 173 3.5% feeds from an AC source of a PV generating station. The distribu- tion line is 10 miles long and has a series impedance of 0.01 + j0.09 2 per mile. The local load is 250 kVA. The balance of power can be injected into the local utility using a 500 kVA, 3.2 kV Y grounded/13.2 kV delta transformer T2 with the per unit reactance of 8%. Assume the voltage base of 13.8 kV on the local power grid side, kVA base of 500, and the DC bus voltage of 800 V. Compute the following: (i) The inverter and the PV generating station ratings. (ii) The per unit impedance diagram of the microgrid.
Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
Related questions
Question
Qusation as per attaced picture
![Consider the microgrid of Figure 3.68. A three-phase 500 kVA, 440 V Y
grounded/3.2 kV delta transformer T1 with the per unit reactance of
3.5
AC bus
Local
DC bus
loads
250 kVA
PV generating
station
DC/ACH
Local
Zrans
Inverter
power
T,
440 V/3.2 kV
grid
3.2 kV T, 13.2 kV
500 kVA
3.5%
3.2/13.2 kV
500 kVA, 8%
Figure 3.68 A one-line diagram of Problem 3.5.
PROBLEMS
173
3.5% feeds from an AC source of a PV generating station. The distribu-
tion line is 10 miles long and has a series impedance of 0.01 + j0.09 2 per
mile. The local load is 250 kVA. The balance of power can be injected
into the local utility using a 500 kVA, 3.2 kV Y grounded/13.2 kV delta
transformer T2 with the per unit reactance of 8%. Assume the voltage
base of 13.8 kV on the local power grid side, kVA base of 500, and the
DC bus voltage of 800 V.
Compute the following:
(i) The inverter and the PV generating station ratings.
(ii) The per unit impedance diagram of the microgrid.](/v2/_next/image?url=https%3A%2F%2Fcontent.bartleby.com%2Fqna-images%2Fquestion%2F2fc617bf-34e2-4dfe-9c82-05711b32c702%2F8d8e95fa-9788-40dd-a2a4-eb8497903a62%2Fh8mqxow_processed.png&w=3840&q=75)
Transcribed Image Text:Consider the microgrid of Figure 3.68. A three-phase 500 kVA, 440 V Y
grounded/3.2 kV delta transformer T1 with the per unit reactance of
3.5
AC bus
Local
DC bus
loads
250 kVA
PV generating
station
DC/ACH
Local
Zrans
Inverter
power
T,
440 V/3.2 kV
grid
3.2 kV T, 13.2 kV
500 kVA
3.5%
3.2/13.2 kV
500 kVA, 8%
Figure 3.68 A one-line diagram of Problem 3.5.
PROBLEMS
173
3.5% feeds from an AC source of a PV generating station. The distribu-
tion line is 10 miles long and has a series impedance of 0.01 + j0.09 2 per
mile. The local load is 250 kVA. The balance of power can be injected
into the local utility using a 500 kVA, 3.2 kV Y grounded/13.2 kV delta
transformer T2 with the per unit reactance of 8%. Assume the voltage
base of 13.8 kV on the local power grid side, kVA base of 500, and the
DC bus voltage of 800 V.
Compute the following:
(i) The inverter and the PV generating station ratings.
(ii) The per unit impedance diagram of the microgrid.
Expert Solution
![](/static/compass_v2/shared-icons/check-mark.png)
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
This is a popular solution!
Trending now
This is a popular solution!
Step by step
Solved in 5 steps with 3 images
![Blurred answer](/static/compass_v2/solution-images/blurred-answer.jpg)
Recommended textbooks for you
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
![Introductory Circuit Analysis (13th Edition)](https://www.bartleby.com/isbn_cover_images/9780133923605/9780133923605_smallCoverImage.gif)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
![Delmar's Standard Textbook Of Electricity](https://www.bartleby.com/isbn_cover_images/9781337900348/9781337900348_smallCoverImage.jpg)
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
![Programmable Logic Controllers](https://www.bartleby.com/isbn_cover_images/9780073373843/9780073373843_smallCoverImage.gif)
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
![Fundamentals of Electric Circuits](https://www.bartleby.com/isbn_cover_images/9780078028229/9780078028229_smallCoverImage.gif)
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
![Electric Circuits. (11th Edition)](https://www.bartleby.com/isbn_cover_images/9780134746968/9780134746968_smallCoverImage.gif)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
![Engineering Electromagnetics](https://www.bartleby.com/isbn_cover_images/9780078028151/9780078028151_smallCoverImage.gif)
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,