3.23 Figure 3.32 shows the oneline diagram of a three-phase power system. By selecting a common base of 100 MVA and 22 kV on the generator side, draw an impedance diagram showing all impedances including the load impedance in per-unit. The data are given as follows: x = 0.18 per unit x = 0.10 per unit x = 0.06 per unit x = 0.064 per unit x = 0.08 per unit x = 0.185 per unit G: 90 MVA 22 kV 50 MVA 22/220 kV T;: 40 MVA 220/11 kV T3: 40 MVA 22/110 kV 40 MVA 110/11 kV М: 66.5 MVA 10.45 kV

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
3.23 Figure 3.32 shows the oneline diagram of a three-phase power system. By
selecting a common base of 100 MVA and 22 kV on the generator side,
draw an impedance diagram showing all impedances including the load
impedance in per-unit. The data are given as follows:
x = 0.18 per unit
x = 0.10 per unit
x = 0.06 per unit
x = 0.064 per unit
x = 0.08 per unit
x = 0.185 per unit
G:
90 MVA
22 kV
T;:
50 MVA
22/220 kV
T;:
40 MVA
220/11 kV
T3:
40 MVA
22/110 kV
40 MVA
110/11 kV
M:
66.5 MVA
10.45 kV
Lines 1 and 2 have series reactances of 48.4 and 65.43 N, respectively. At
bus 4, the three-phase load absorbs 57 MVA at 10.45 kV and 0.6 power
factor lagging.
FIGURE 3.32
3
Line 1
Problem 3.23
220 kV
G
M
Line 2
Load
110 kV
CO
Transcribed Image Text:3.23 Figure 3.32 shows the oneline diagram of a three-phase power system. By selecting a common base of 100 MVA and 22 kV on the generator side, draw an impedance diagram showing all impedances including the load impedance in per-unit. The data are given as follows: x = 0.18 per unit x = 0.10 per unit x = 0.06 per unit x = 0.064 per unit x = 0.08 per unit x = 0.185 per unit G: 90 MVA 22 kV T;: 50 MVA 22/220 kV T;: 40 MVA 220/11 kV T3: 40 MVA 22/110 kV 40 MVA 110/11 kV M: 66.5 MVA 10.45 kV Lines 1 and 2 have series reactances of 48.4 and 65.43 N, respectively. At bus 4, the three-phase load absorbs 57 MVA at 10.45 kV and 0.6 power factor lagging. FIGURE 3.32 3 Line 1 Problem 3.23 220 kV G M Line 2 Load 110 kV CO
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 8 steps with 2 images

Blurred answer
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,