2.1 Two power stations, A and B, are synchronized at 66 kV. They are inter-connected by a transmission line with an inductive reactance of 6.7-Ω and resistance of 3.5-Ω per phase. The voltage of power station A is advanced with an angle of 10.5 degrees with respect to the voltage of power station B. The loading of power station B has a real power of 200 MW. The respective loads of the two power stations are as follows: Power station A: 165 MVA at a power factor of 0.819 lagging. Power station B: The reactive power consumed by the load is 155 Mvar. *Round off to two decimal places to every question 15.The active power loss within the interconnector (MW). 16.The reactive power loss within the interconnector (MVar). 17.The final loading of power station A (MVA) and it's angle
2.1 Two power stations, A and B, are synchronized at 66 kV. They are inter-connected
by a transmission line with an inductive reactance of 6.7-Ω and resistance of 3.5-Ω per
phase. The voltage of power station A is advanced with an angle of 10.5 degrees with
respect to the voltage of power station B. The loading of power station B has a real
power of 200 MW. The respective loads of the two power stations are as follows:
Power station A: 165 MVA at a power factor of 0.819 lagging.
Power station B: The reactive power consumed by the load is 155 Mvar.
*Round off to two decimal places to every question
15.The active power loss within the interconnector (MW).
16.The reactive power loss within the interconnector (MVar).
17.The final loading of power station A (MVA) and it's angle
Step by step
Solved in 5 steps with 5 images