18. A balanced three-phase loads draws 20 kW at 0.447 pf. Lagging from a 230 V, 60 Hz, three-phase transmission lines. Find the reading of the two wattmeter s properly connected to measure power a. 18.45 kW, 1.55 kW b. 21.55 kW, -1.55 kW c. 14.25 kW, 5.75 kW, d. 25.75 kW, -5.75 kW

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
18. A balanced three-phase loads draws 20 kW at 0.447 pf. Lagging from a 230 V, 60 Hz, three-phase
transmission lines. Find the reading of the two wattmeter s properly connected to measure power
c. 14.25 kW, 5.75 kw,
d. 25.75 kW, -5.75 kW
a. 18.45 kW, 1.55 kW
b. 21.55 kW, -1.55 kW
19. Two watt-meter method is applied to a 3-phase motor running at full-load. The two wattmeter indicate 85.5
kW and 34.7 kW. What is the operating p.f. of the motor?
a. 87.45%
b. 89.49%
c. 80.69%
d. 94.76%
20. A 3-phase feeder carries two lagging balance loads. The power observed by each is measured by two
wattmeter method, giving the following reading
1" load: W, = 160 kw W2 = 96 kW
2nd load: W, = 90 kw W, = 48 kW
What is the combined kVA load on the feeder?
a. 434.68
b. 504.24
c. 462.35
d. 420.12
Transcribed Image Text:18. A balanced three-phase loads draws 20 kW at 0.447 pf. Lagging from a 230 V, 60 Hz, three-phase transmission lines. Find the reading of the two wattmeter s properly connected to measure power c. 14.25 kW, 5.75 kw, d. 25.75 kW, -5.75 kW a. 18.45 kW, 1.55 kW b. 21.55 kW, -1.55 kW 19. Two watt-meter method is applied to a 3-phase motor running at full-load. The two wattmeter indicate 85.5 kW and 34.7 kW. What is the operating p.f. of the motor? a. 87.45% b. 89.49% c. 80.69% d. 94.76% 20. A 3-phase feeder carries two lagging balance loads. The power observed by each is measured by two wattmeter method, giving the following reading 1" load: W, = 160 kw W2 = 96 kW 2nd load: W, = 90 kw W, = 48 kW What is the combined kVA load on the feeder? a. 434.68 b. 504.24 c. 462.35 d. 420.12
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Analysis of Single Phase and Three Phase System
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,