14. For a power plant with two units, the weekly load is 1200 MW. The coal consumption Q (tons/hour) for each unit is Q₁=16+.3P₁ tons/hours Q2-25+.4P₂ tons/h The total coal available to the plant is limited to 90,000 tons/week. If the linear cost curves are given as C₁=495+11P₁ $/hour, C₂=760+10P₂ $/hour And generation by each unit is limited to 150 ≤ P₁ ≤ 600MW Determine the values of P₁ and P₂ for minimizing the cost of power generation. " 400 ≤P₂ ≤1000MW

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
14. For a power plant with two units, the weekly load is 1200 MW. The coal consumption
(tons/hour) for each unit is Q₁ 16+.3P₁ tons/hours
Q2-25+.4P₂ tons/h
The total coal available to the plant is limited to 90,000 tons/week.
If the linear cost curves are given as C₁=495+11P₁ $/hour, C₂-760+10P₂ $/hour
And generation by each unit is limited to 150 ≤ P, ≤ 600MW
Determine the values of P₁ and P₂ for minimizing the cost of power generation.
15. Use LP to determine economic dispatch if C₁ = 5+ 3P₁, C₂ = 7+6P2, C3 = 8 + 9P3
50 P₁ < 150 MW
and
PD=210 MW
If the line flow P12= .3P₁ + .4P₂ + .1P3, also determine P₁, P₂ and P3 so that P₁2 is limited to 70
MW.
1
4
400 ≤ P₂ ≤1000MW
H
2
3
Transcribed Image Text:14. For a power plant with two units, the weekly load is 1200 MW. The coal consumption (tons/hour) for each unit is Q₁ 16+.3P₁ tons/hours Q2-25+.4P₂ tons/h The total coal available to the plant is limited to 90,000 tons/week. If the linear cost curves are given as C₁=495+11P₁ $/hour, C₂-760+10P₂ $/hour And generation by each unit is limited to 150 ≤ P, ≤ 600MW Determine the values of P₁ and P₂ for minimizing the cost of power generation. 15. Use LP to determine economic dispatch if C₁ = 5+ 3P₁, C₂ = 7+6P2, C3 = 8 + 9P3 50 P₁ < 150 MW and PD=210 MW If the line flow P12= .3P₁ + .4P₂ + .1P3, also determine P₁, P₂ and P3 so that P₁2 is limited to 70 MW. 1 4 400 ≤ P₂ ≤1000MW H 2 3
Expert Solution
steps

Step by step

Solved in 2 steps

Blurred answer
Knowledge Booster
Types of Power Station and Its Characteristics
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,