1. A working area with a general dimension of 24 ft by 30 ft is lighted with 10 fixtures of four F40 T10 fluorescent lamp (3550 lumens). Calculate the maintained illumination assuming that CU is 0.35 and LLF is 0.70.

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter1: Atomic Structure
Section: Chapter Questions
Problem 6RQ: How many valence electrons are generally contained in materials used for insulators?
icon
Related questions
Question

1. A working area with a general dimension of 24 ft by 30 ft is lighted with 10 fixtures of four F40 T10 fluorescent lamp (3550 lumens). Calculate the maintained illumination assuming that CU is 0.35 and LLF is 0.70.           

2. The resistivity of a copper rod 50 feet long and 0.25 inch in diameter is 1.72 μΩ-cm at 20 0C. What is its resistance at -20 0C?                                     