Example 5.5 (chp5ex5) A three-phase, 60-Hz, 500-kV transmission line is 300 km long. The line induc- tance is 0.97 mH/km per phase and its capacitance is 0.0115 F/km per phase. Assume a lossless line. (a) Determine the line phase constant 3, the surge impedance Zc, velocity of prop- agation v and the line wavelength A. (b) The receiving end rated load is 800 MW, 0.8 power factor lagging at 500 kV. Determine the sending end quantities and the voltage regulation.

Introductory Circuit Analysis (13th Edition)
13th Edition
ISBN:9780133923605
Author:Robert L. Boylestad
Publisher:Robert L. Boylestad
Chapter1: Introduction
Section: Chapter Questions
Problem 1P: Visit your local library (at school or home) and describe the extent to which it provides literature...
icon
Related questions
Question
AEx 5.5 solution.pdf - Adobe Acrobat Reader DC (32-bit)
Dosya Düzenle Görünüm įmzalama Pencere Yardım
Ex5.1 s.
Ex5.5 s.. x
Ex5.6 s.
Ex5.7 s.
Ex5.8 s...
E>
Ana Sayfa
Araçlar
PowerP.
PowerP..
図Q
1 / 2
Example 5.5
(chp5ex5)
A three-phase, 60-Hz, 500-kV transmission line is 300 km long. The line induc-
tance is 0.97 mH/km per phase and its capacitance is 0.0115 uF/km per phase.
Assume a lossless line.
(a) Determine the line phase constant 3, the surge impedance Ze, velocity of prop-
agation v and the line wavelength A.
(b) The receiving end rated load is 800 MW, 0.8 power factor lagging at 500 kV.
Determine the sending end quantities and the voltage regulation.
Transcribed Image Text:AEx 5.5 solution.pdf - Adobe Acrobat Reader DC (32-bit) Dosya Düzenle Görünüm įmzalama Pencere Yardım Ex5.1 s. Ex5.5 s.. x Ex5.6 s. Ex5.7 s. Ex5.8 s... E> Ana Sayfa Araçlar PowerP. PowerP.. 図Q 1 / 2 Example 5.5 (chp5ex5) A three-phase, 60-Hz, 500-kV transmission line is 300 km long. The line induc- tance is 0.97 mH/km per phase and its capacitance is 0.0115 uF/km per phase. Assume a lossless line. (a) Determine the line phase constant 3, the surge impedance Ze, velocity of prop- agation v and the line wavelength A. (b) The receiving end rated load is 800 MW, 0.8 power factor lagging at 500 kV. Determine the sending end quantities and the voltage regulation.
Expert Solution
steps

Step by step

Solved in 4 steps

Blurred answer
Knowledge Booster
Compensation Techniques in Transmission Line
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
Recommended textbooks for you
Introductory Circuit Analysis (13th Edition)
Introductory Circuit Analysis (13th Edition)
Electrical Engineering
ISBN:
9780133923605
Author:
Robert L. Boylestad
Publisher:
PEARSON
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning
Programmable Logic Controllers
Programmable Logic Controllers
Electrical Engineering
ISBN:
9780073373843
Author:
Frank D. Petruzella
Publisher:
McGraw-Hill Education
Fundamentals of Electric Circuits
Fundamentals of Electric Circuits
Electrical Engineering
ISBN:
9780078028229
Author:
Charles K Alexander, Matthew Sadiku
Publisher:
McGraw-Hill Education
Electric Circuits. (11th Edition)
Electric Circuits. (11th Edition)
Electrical Engineering
ISBN:
9780134746968
Author:
James W. Nilsson, Susan Riedel
Publisher:
PEARSON
Engineering Electromagnetics
Engineering Electromagnetics
Electrical Engineering
ISBN:
9780078028151
Author:
Hayt, William H. (william Hart), Jr, BUCK, John A.
Publisher:
Mcgraw-hill Education,