EET-115 Lab 9 - Grounding & Service Mast
pdf
keyboard_arrow_up
School
Centennial College *
*We aren’t endorsed by this school
Course
115
Subject
Electrical Engineering
Date
Jan 9, 2024
Type
Pages
3
Uploaded by CorporalMeerkat3730
Page
1
of
3
Centennial College
Electrical Engineering Technician / Technology
EET-115 Installation Methods 1
Name:
Student #:
Section:
Date:
LAB #9
Grounding and Service Mast
Objectives:
•
To understand all theory reviewed and identify all parts associated with a 200 Amp overhead
service. To describe the procedures used to install an underground service as per diagram below.
Materials & Tools Required:
●
Meter Base
●
#3 AWG T-90 Conductor
●
Electrical Panel (Combination)
●
Knife
●
Hacksaw
●
Hex Keys
●
Band Saw
●
Screwdrivers (Various)
Page
2
of
3
Questions:
State the
CEC Rule
number if the code book is used.
1.
According to the CEC, can PVC pipe be used for an outdoor residential overhead service mast?
2.
The point of attachment of supply or consumer’s service conductors or cables shall be not less than
_______ across highways, streets, lanes, and alleys.
3.
How high must the consumer’s service head or
equivalent be installed above the support for
attachment of the overhead service conductors?
4.
The point of attachment of supply or consumer’s service conductors or cables shall not exceed
________ above grade or sidewalk.
5.
What is the minimum size grounding conductor to be installed for a 200 Amp residential service?
Diagram:
Complete the diagram below by labelling indicated parts.
Page
3
of
3
QUESTIONS
DIAGRAM
TOTAL MARK
5
10
15
Instructor Signature
Your preview ends here
Eager to read complete document? Join bartleby learn and gain access to the full version
- Access to all documents
- Unlimited textbook solutions
- 24/7 expert homework help
Related Documents
Related Questions
h.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0.
h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.
arrow_forward
The term "____" is defined in NEC® Article 100 as "connected to establish electrical continuity and conductivity."
Select one:
A. BENDED (BENDING)
B. BONDED (BONDING)
C. SHUNTED (SHUNTING)
D. GROUNDED (GROUNDING)
arrow_forward
7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.
arrow_forward
1. _______ is not considered an effective ground-fault current path. a) Ground b) Equipment grounding conductors c) Equipment bonding jumpers d) Grounded conductors
2.Which of the following is not a conductor in the grounding and bonding scheme for an ungrounded system? a) Grounding electrode conductor for grounding equipment enclosures and conductive parts b) Equipment grounding conductor c) Bonding conductors or jumper d) System grounded conductor
arrow_forward
list the material required for overhead service connection
arrow_forward
Underground service conductors shall have [Fill-in-the-blank].
A)adequate mechanical strength.
B)sufficient ampacity for the loads calculated.
C)none of these.
D)adequate mechanical strength and sufficient ampacity for the loads calculated.
arrow_forward
Describe and discuss the electrical load requirements for different types of buildings.
arrow_forward
pls help
arrow_forward
c.1. Which of the following is one of the three essential functions of an equipment grounding conductor?A. Provide an arc-fault current pathB. Establish groundingC. Establish bondingD. Ensure the system is groundedc.2. What's another name for the three-point method of Earth resistance testing?A. Fall-of-potentialB. Line surgeC. Spatial shieldingD. Leakage current
c.3. If the National Electrical Code provides a requirement to ground equipment, it generally implies thatthere will be a direct connection to the Earth of a connection through a/anA. grounding electrode conductor.B. equipment grounding conductor.C. equipotential bonding conductor.D. bonding conductor.
arrow_forward
A? Conductor is defined in NEC 240.2 as a conductor, other than a service conductor, having overcurrent protection ahead of its point of supply that exceeds the value permitted for similar conductors that are not taps.
A. Faulted b. Tap c. Magnetic d. Copper-like
arrow_forward
Grounding lighting fixtures. Threre are specific requirements for grounding lighting fixtures. How must they be grounded and with what size conductors?
arrow_forward
H2. A/An _______ is an insulating tube or sleeve that protects an electrical conductor where it passesthrough a hole.A. expansion fittingB. couplingC. gland nutD. bushing
H3. Conductors that are larger than AWG size 8 will come only as a/an _______ conductor.A. aluminumEnd of examB. coveredC. solidD. stranded
arrow_forward
4 Describe the various methods of laying underground cables. What are the relative advantages anddisadvantages of each method?
arrow_forward
Most residential general lighting circuits are wired with 14-AWG copper conductors and are protected by 15-amp circuit breakers. However, there are many electricians who install 12-AWG copper conductors and protect them with 20-amp circuit breakers. How will you know which conductor size and which circuit breaker size will be used for the general lighting branch circuits in the house you are wiring?
arrow_forward
20.a. What's the primary disadvantage of using copper conductors?A. DurabilityB. CostC. AvailabilityD. Weight20.b. The NEC requires that each service-disconnecting means be suitable forA. hazardous locations.B. disconnecting the meter.C. wet conditions.D. the prevailing conditions
20.c. As a general rule, each building or structure is limited to a single service. What's an automatic exceptionto this rule?A. A second service deemed suitable for useB. A second service having the proper markingsC. Emergency systems or fire pumpsD. Higher building occupancy
arrow_forward
Question A
arrow_forward
SEE MORE QUESTIONS
Recommended textbooks for you

EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT
Related Questions
- h.1. In an alternating-current system, the maximum size for a copper grounding electrode conductor isA. 250 kcmil.B. 3/0.C. 500 kcmil.D. 4/0. h.2. The figure shows a fault condition in an ungrounded electrical system. Which of the following will occurbecause of the fault in this system?A. Only the overcurrent protector at Point A will trip open.B. The ground fault will heavily damage the service.C. Nothing will happen until a second ground fault occurs.D. The overcurrent protection will trip, shutting off all the line side power.arrow_forwardThe term "____" is defined in NEC® Article 100 as "connected to establish electrical continuity and conductivity." Select one: A. BENDED (BENDING) B. BONDED (BONDING) C. SHUNTED (SHUNTING) D. GROUNDED (GROUNDING)arrow_forward7.B. The size of a grounding electrode conductor for a service or separately derived system is generally basedon the size of the largestA. ungrounded supply conductor.B. equipment grounding conductor.C. grounded electrode.D. bonding jumper.7.C. Which of the following statements about bonding is true?A. The joint or termination must offer opposition in the circuit for effective electrical connections.B. Effective bonding keeps impedance high if a fault should occur.C. The entire electrical safety circuit is only as good as its strongest bonded link.D. Bonding connections must endure high levels of fault current until overcurrent protective devices can operate.arrow_forward
- 1. _______ is not considered an effective ground-fault current path. a) Ground b) Equipment grounding conductors c) Equipment bonding jumpers d) Grounded conductors 2.Which of the following is not a conductor in the grounding and bonding scheme for an ungrounded system? a) Grounding electrode conductor for grounding equipment enclosures and conductive parts b) Equipment grounding conductor c) Bonding conductors or jumper d) System grounded conductorarrow_forwardlist the material required for overhead service connectionarrow_forwardUnderground service conductors shall have [Fill-in-the-blank]. A)adequate mechanical strength. B)sufficient ampacity for the loads calculated. C)none of these. D)adequate mechanical strength and sufficient ampacity for the loads calculated.arrow_forward
- Describe and discuss the electrical load requirements for different types of buildings.arrow_forwardpls helparrow_forwardc.1. Which of the following is one of the three essential functions of an equipment grounding conductor?A. Provide an arc-fault current pathB. Establish groundingC. Establish bondingD. Ensure the system is groundedc.2. What's another name for the three-point method of Earth resistance testing?A. Fall-of-potentialB. Line surgeC. Spatial shieldingD. Leakage current c.3. If the National Electrical Code provides a requirement to ground equipment, it generally implies thatthere will be a direct connection to the Earth of a connection through a/anA. grounding electrode conductor.B. equipment grounding conductor.C. equipotential bonding conductor.D. bonding conductor.arrow_forward
- A? Conductor is defined in NEC 240.2 as a conductor, other than a service conductor, having overcurrent protection ahead of its point of supply that exceeds the value permitted for similar conductors that are not taps. A. Faulted b. Tap c. Magnetic d. Copper-likearrow_forwardGrounding lighting fixtures. Threre are specific requirements for grounding lighting fixtures. How must they be grounded and with what size conductors?arrow_forwardH2. A/An _______ is an insulating tube or sleeve that protects an electrical conductor where it passesthrough a hole.A. expansion fittingB. couplingC. gland nutD. bushing H3. Conductors that are larger than AWG size 8 will come only as a/an _______ conductor.A. aluminumEnd of examB. coveredC. solidD. strandedarrow_forward
arrow_back_ios
SEE MORE QUESTIONS
arrow_forward_ios
Recommended textbooks for you
- EBK ELECTRICAL WIRING RESIDENTIALElectrical EngineeringISBN:9781337516549Author:SimmonsPublisher:CENGAGE LEARNING - CONSIGNMENT

EBK ELECTRICAL WIRING RESIDENTIAL
Electrical Engineering
ISBN:9781337516549
Author:Simmons
Publisher:CENGAGE LEARNING - CONSIGNMENT